22
4. System Configurations
Test run procedural flow
1. System startup (*)
Configure the settings needed for the local system.
Refer to page 23 for details.
2. Air bleeding operation
Operate the unit’s pump to perform the air bleeding operation.
Refer to page 33 for details.
3. Water flow rate adjustment operation
Adjust the unit’s pump and flow rate adjustment valve.
Refer to pages 35 and 37 for details.
* If multiple units are connected to the same water circuit, perform the water flow rate adjustment operation for each unit simultaneously.
(*)
Request at the Time of a Test Run
Set the slide switch SWS2 on the board inside the control box to the “lower side” during the test run.
By default, it is set to the “upper side” for forced stop of the pump and compressor to prevent the pump being
damaged by the anti-freezing process in no water passing status or valve closed status before the test run.
[1] Schematic Diagrams of Individual and Multiple Systems
(1) Individual system
(2) Multiple system (2-16 units)
Refer to the sections “[2] Switch Types and the Factory Settings” (page 23) and
“(3) System configuration procedures: Individual system” (page 27) for further details.
Refer to the sections “[2] Switch Types and the Factory Settings” (page 23) and
“(4) System configuration procedures : Multiple system” (page 29) for further details.
Unit (MAIN circuit)
PCB
External
temperature
sensor
Field-supplied dry contact
switch/relay or remote
controller (PAR-W31MAA) or
centralized controller (AE-200)
Field-supplied dry contact
switch/relay or remote
controller (PAR-W31MAA) or
centralized controller (AE-200)
External
temperature
sensor
Unit (MAIN circuit)
PCB
* Each unit is operated individually by connecting a dry contact switch/relay to each unit.
External
temperature
sensor
Field-supplied dry contact
switch/relay or remote
controller (PAR-W31MAA) or
centralized controller (AE-200)
MAIN unit
SUB unit
SUB unit(s)
n units
Inter-unit wiring
(M-NET line)
Inter-unit wiring
(M-NET line)
Unit (MAIN circuit)
PCB
Unit (MAIN circuit)
PCB
Unit (MAIN circuit)
PCB
* A group of unit that consists of one main unit and up to 15 sub units is operated collectively by connecting an external water temperature sensor and a dry
contact switch/relay to the main unit.