Control cable specifications
*1 Use a CVVS or CPEVS cable (Max. total length of 200 m) if there is a source of electrical interference near by (e.g., factory) or the total length of control wiring
exceeds 120 m.
*2 When the wiring length exceeds 10 m, use wire of 1.25 mm
2
.
Remote controller cable
Size
0.3 - 1.25 mm² (Max. 200 m total)*2
Recommended cable types
CVV
M-NET cable between units
*1
Size
Min. 1.25 mm² (Max. 120 m total)
Recommended cable types
Shielded cable CVVS, CPEVS or MVVS
External input wire size
Min. 0.3 mm²
External output wire size
1.25 mm²