<2> Multiple unit installation
When installing multiple units, make sure to take into consideration factors such as providing enough space for
people to pass through, ample space between blocks of units, and sufficient space for airflow. (The areas marked
with
Ⓐ
in the figures below must be left open.)
In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1"
through "h3" in the figures) to L1, L2, and L3 as shown in the tables below.
(1) Side-by-side installation
(2) Face-to-face installation
h2
L2
L1
h1
L4
Ⓐ
Ⓐ
[mm]
Unit height
500
Required minimum distance [mm]
L1 (Front)
L2 (Rear)
L4 (Between)
500 + h1
300 + h2
100
Ⓐ
Leave open in two directions.
When there are walls in the front and rear of
the block of units
h1
h2
L1
L4
L4
L2
Ⓐ
Ⓐ
500
Unit height
Required minimum distance [mm]
L1 (Front)
L2 (Rear)
L4 (Between)
500 300
500
Ⓐ
Leave open in two directions.
When there is a wall on either the right or left
side of the block of units
h3
L4
L3
L4
Unit height
Required minimum distance [mm]
L3 (Right/Left)
L4 (Between)
50 + h3
500