18
3
Configuration method and selection criteria of flow rate adjustment device
In this system, a flow rate adjustment device is installed in the secondary side circuit to perform secondary side
flow rate adjustment control by outputting 0 to 10 V from the unit.
* 10-V power supply is not supplied.
The following shows a system configuration example of the flow rate adjustment device and notes on the
system configuration.
The following three system types are recommended as flow rate adjustment devices:
1. System using a three-way valve
2. System using a two-way valve
3. System using an inverter
1. System using a three-way valve
Notes on selection method and system configuration
Notes on pump selection and connection
• Calculate the total pump head according to the system at the site and then select a pump capable of outputting
the minimum flow rate of about 3
ℓ
/min and maximum flow rate of about 30
ℓ
/min with the necessary pump head
for the piping at the site.
• When selecting the pump, please note that output at a high flow rate will not occur if the flow rate with the pump
head of the system at the site is low, and output at a low flow rate will not occur if the flow rate is too high.
• Be sure to check that the flow rate becomes 20 to 30
ℓ
/min at the maximum output during a flow rate adjustment
test run (refer to page 37).
For how to check the flow rate, refer to page 38.
* If the flow rate is not within the range of 20 to 30
ℓ
/min, select a different pump or adjust the maximum frequency
using an inverter, etc. so that the maximum flow rate of 20 to 30
ℓ
/min is achieved.
* To select a proper pump, first select a pump that supports slightly high flow rate, and then adjust the frequency
with an inverter so that the flow rate becomes 20 to 30
ℓ
/min at the maximum output.
(In that case, an inverter is necessary to be prepared separately.)
Notes on three-way valve selection and connection
• Use a valve that is capable of adjusting the flow rate with a 0 to 10 V input.
• Calculate the Cv value and select a valve that supports an appropriate rate.
• Select a valve of which the ratio of the maximum flow rate and the minimum flow rate will be at least 1:10.
• Place the three-way valve downstream of the pump. Connect one outlet to the heat exchanger.
Connect the other outlet to the lower part of the tank.
• Carefully read the instruction manual and use the three-way valve in accordance with the usage procedures.
Overview of system
This system has a pump provided at the outlet
of the tank and a three-way valve provided
downstream of the pump, and adjusts the flow
rate by controlling the opening and closing of
the three-way valve.
Flow rate
output device
Flow rate
adjustment
device
Pump
Three-way
valve
Wiring
connection
places
1-3 of CN512 of
control board
(ON/OFF output)
Sub box
terminal block
No. 10, 11, 12
ON/OFF signal
0 to 10 V output
Three-way
valve
Pump