62
5101
Thermistor
fault
Discharge temp sensor (TH1)
Broken or shorted thermistor wiring
5102
Suction temp sensor (TH2)
Broken or shorted thermistor wiring
5103
Heat exchanger
outlet refrigerant temp sensor (TH3)
Broken or shorted thermistor wiring
5104
Air-side heat exchanger
inlet refrigerant temp sensor (TH4)
Broken or shorted thermistor wiring
5105
Air-side heat exchanger
outlet refrigerant temp sensor (TH5)
Broken or shorted thermistor wiring
5109
Outside temp sensor (TH9)
Broken or shorted thermistor wiring
5111
Outlet water temp sensor (TH11)
Broken or shorted thermistor wiring
5112
Inlet water temp sensor (TH12)
Broken or shorted thermistor wiring
5114
Shell temp sensor (TH14)
Broken or shorted thermistor wiring
5115
External water sensor1 (TH15)
Broken or shorted thermistor wiring
5116
External water sensor2 (TH16)
Broken or shorted thermistor wiring
5117
External water sensor3 (TH17)
Broken or shorted thermistor wiring
5118
(when the
secondary
side
control is
enabled)
Secondary side water sensor (TH18)
Broken or shorted thermistor wiring
5201
High-pressure sensor fault/high-pressure fault
Broken or shorted pressure sensor wiring
5202
Low-pressure sensor fault/low-pressure fault
Broken or shorted pressure sensor wiring
1102
Discharge temperature fault
• Water flow control valve fault
• Pump fault
• High-pressure sensor fault
• Discharge refrigerant thermistor fault
• Linear expansion valve fault (Main circuit
LEV, injection LEV)
• Refrigerant shortage (gas leakage)
1105
Heat exchanger outlet temperature fault
• Water flow control valve fault
• Pump fault
1502
Liquid refrigerant floodback
• Fan motor error/broken motor wire
• Low-pressure sensor fault
• Discharge refrigerant temperature
thermistor fault
• Electronic expansion valve fault
7113
Model setting error 1
Dip switches on the PCB were set
incorrectly during maintenance.
7117
Model setting error 2
• Resistor Z21 fault (connected to the Main
control board)
4115
Power supply frequency fault
Power supply frequency is a frequency
other than 50 Hz or 60 Hz.
4102
Open phase
There is an open phase.
• Circuit board fault
Error
code *1
(PCB *2
RC
M-NET)
Error type
Cause
(Installation/Setting error)
Cause
(Parts problems)
Error reset *3
Unit
side
(PCB)
Remote
SWS1 Operation
SW
WT08219X05.book 62 ページ 2018年10月1日 月曜日 午後7時47分