57
Symbol explanation
Symbol
explanation
F02
Electronic expansion valve (Injection)
M
PSL1
Low pressure sensor
F06
Z21
SV1
SV2
Solenoid valve (Defrost)1
Solenoid valve (Defrost)2
High pressure switch
LEV3
Electromagnetic relay (Inverter main circuit)
DC reactor
Ac current sensor
Capacitor (Electrolysis)
Crankcase heater (for heating the compressor)
Electronic expansion valve (Main circuit)
CT22
CT12
DCL
C100
72C
CT3
LEV1
Thermistor
*TH15
〜
18
MS
R1
R5
H1
High pressure sensor
Earth leakage breaker
IGBT
temperature
Fuse
TH1
〜
5,9,1
1,12,14
*S2,3
<
ELB1
>
F01
THHS
F04
F03
F07
PSH1
Compressor motor
Electrical resistance
Function setting connector
Fan motor
63H1
1.
The broken lines indicate the optional parts,field-supplied parts,and field work.
2. Dashed lines indicate sub box
7. When cabtyre cable is used for the control cable wiring,
use a separate cabtyre cable for the following wiring.
Using the same cabtyre cable may cause malfunctions
and damage to the unit.
(a) Optional remote controller wiring
(b) No-voltage contact input wiring
(c) No-voltage contact output wiring
(d) Remote water temperature setting
8. Use a contact that takes 12VDC 1mA
for no-voltage contact input.
6. Leave a space of at least 5 cm between the low voltage external wiring
(no-voltage contact input and remote controller wiring) and wiring of 100V
or greater
.Do not place them in the same conduit tube or cabtyre cable as
this will damage the circuit board.
F121
H2
Electric heater (Antifreeze)
MP1
Pump motor
MVW1
W
ater flow control valve
SV3
SV4
Solenoid valve (Defrost)3
Solenoid valve (Defrost)4
SV5
Solenoid valve (Injection circuit)
S1
W
ater flow rate sensor
W
ater flow rate sensor
Thermistor
* of symbol item is the optional parts, <> is field-supplied parts.
3. Faston terminals have a locking function.
Press the tab in the middle of the terminals to remove them.
Check that the terminals are securely locked in place after insertion.
4.
The symbols of the field connecting terminals are as follows.
:T
erminal block
:Connection by cutting the short circuit wire
5.
The method of input signal of operation can choose one of optinal remote controller
or no-voltage input.
10
.
Use a 4-20mA
signal output device with insulation.
Feeding 30mA
or more current may damage the circuit board.
11
.
For prevention of damage of the pump, SWS2 is set in "A"(factory setting).
12
.
Use a contact that takes 250V
AC, 10mA
or above, and 1A
or below for no-voltage
contact output.
Change the slide switch SWS2
「
B(automatic)
」
in
T
est Run.
R1
1
R12
Resistance (for W
ater flow rate sensor 2)
Resistance (for W
ater flow rate sensor 3)
OFF
OFF
OFF
OFF
2
〜
10V
1
〜
5V
0
〜
10V
4
〜
20mA
ON
ON
ON
SW421-1
SW421-2
OFF
9. Need to selects either W
ater temperature setting input signal.
Set the SW421 as shown in the table below
.
Note
WT08219X05.book 57 ページ 2018年10月1日 月曜日 午後7時47分