45
2
Outlet hot water temperature setting method from PCB
3
Settings from PAR-W31MAA
Refer to page 75.
Setting procedures
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF setting is set to OFF. *
Step 1
Set the dip switches
SW2 and SW3.
Set the dip switches on the circuit board as follows before making the settings for the items
described in this section.
Step 2
Select the desired
item with the push
switch SWP3.
Press the push switch SWP3 to select item code 2.
Press the push switches SWP1 or SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.
Step 3
Press the push
switches SWP1 (
↑
)
or SWP2 (
↓
) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
SW2
SW3
-10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
OFF
ON
OFF
Settings table
* This becomes the secondary side outlet hot water temperature when the secondary side
control is enabled.
* Secondary control disabled: 90ºC, Secondary control enabled: 80ºC
Items that can be set
Item
code
Initial
value
Unit
Setting
Setting change
from an optional
remote controller
Increments
Lower
limit
Upper
limit
Outlet Hot Water Temp. setting
9
65
ºC
0.5
40
*90 (80)
Possible
WT08219X05.book 45 ページ 2018年10月1日 月曜日 午後7時47分