63
4250
4255
(
101
)
Inverter
error
Electric
current
related
errors
during
operation
IPM error
• INV board fault (4250)
• Fan board fault (4255)
• Ground fault of the compressor
• Coil problem
• IPM error (loose terminal screws,
cracked due to swelling)
• Items listed under "Heatsink overheat
protection" below
4250
4255
(
102
)
ACCT overcurrent
• INV board fault (4250)
• Fan board fault (4255)
• Ground fault of the compressor
• Coil problem
• IPM error (loose terminal screws,
cracked due to swelling)
4250
4255
(
103
)
DCCT overcurrent
4250
4255
(
106
)
Overcurrent relay trip
(momentary value) (During
operation)
4250
4255
(
107
)
Overcurrent relay trip (effective
value) (During operation)
4250
4255
(
104
)
Short-circuited IPM/ground fault
(During operation)
• Ground fault of the compressor
• IPM error (loose terminal screws,
cracked due to swelling)
4250
4255
(
105
)
Overcurrent error due to a short-
circuited (During operation)
Inter-phase voltage drop
(Inter-phase voltage at or below 180 V)
• Ground fault of the compressor
• Shorted output wiring
4250
4255
(
101
)
Current
related
prob-
lems at
start up
IPM error
(At startup)
• INV board fault (4250)
• Fan board fault (4255)
• Ground fault of the compressor
• Coil problem
• IPM error (loose terminal screws,
cracked due to swelling)
• Items listed under "Heatsink overheat
protection" below
4250
4255
(
102
)
ACCT overcurrent
(At startup)
• INV board fault (4250)
• Fan board fault (4255)
• Ground fault of the compressor
• Coil problem
• IPM error (loose terminal screws,
cracked due to swelling)
4250
4255
(
103
)
DCCT overcurrent
(At startup)
4250
4255
(
106
)
Overcurrent relay trip
(momentary value) (At startup)
4250
4255
(
107
)
Overcurrent relay trip
(effective value) (At startup)
Error
code *1
(PCB *2
RC
M-NET)
Error type
Cause
(Installation/Setting error)
Cause
(Parts problems)
Error reset *3
Unit
side
(PCB)
Remote
SWS1 Operation
SW
WT08219X05.book 63 ページ 2018年10月1日 月曜日 午後7時47分