3 BASIC FUNCTION
3.4 Stroke limit function [G] [WG]
97
3
Servo parameter list
The settings related to the stroke limit function can be performed directly with the servo parameters. Perform the settings as
required.
Servo
parameter
Symbol
Name
Outline
PC19.0
*COP6
[AL. 099 Stroke limit warning]
selection
Enable or disable [AL. 099 Stroke limit warning].
When "Disabled" is selected, [AL. 099 Stroke limit warning] does not occur when LSP
(Forward rotation stroke end) or LSN (Reverse rotation stroke end) is off, but the
stroke limit does still stop the operation.
0: Enabled (initial value)
1: Disabled
PD01.2
*DIA1
Input signal automatic ON
selection
LSP (Forward rotation stroke end) and LSN (Reverse rotation stroke end) can be set
to "Disabled" (use for an external input signal.) or "Enabled" (Automatic on).
Initial value: 0h (Disabled (Use for an external input signal.))
PD03.0-1
*DI1
Device selection
Any input device can be assigned to the CN3-2 pin.
Initial value: 0Ah (LSP (Forward rotation stroke end))
PD04.0-1
*DI2
Device selection
Any input device can be assigned to the CN3-12 pin.
Initial value: 0Bh (LSN (Reverse rotation stroke end))
PD05.0-1
*DI3
Device selection
Any input device can be assigned to the CN3-19 pin.
Initial value: 22h (DOG (Proximity dog))
PD41.2
*DOP4
Limit switch enabled status
selection
0: Limit switch always enabled (initial value)
1: Enabled only for homing mode
PD41.3
*DOP4
Sensor input method selection
0: Input from servo amplifier (LSP/LSN/DOG) (initial value)
1: Input from controller (C_FLS/C_RLS/C_DOG)
PL08.2
*LIT3
Magnetic pole detection - Stroke
limit enabled/disabled selection
Select whether to enable or disable the stroke limit function during magnetic pole
detection.
0: Enabled (initial value)
1: Disabled