4 APPLICABLE FUNCTIONS
4.3 Scale measurement function [G] [WG]
169
4
Selecting a polarity of the scale measurement encoder
Select the polarity of the scale measurement encoder in [Pr. PC27.0 Encoder pulse count polarity selection] and set [Pr.
PC27.2 ABZ phase input interface encoder ABZ phase connection assessment function selection] shown below as required.
Precautions
[Pr. PC27.0 Encoder pulse count polarity selection] is not related to [Pr. PA14 Travel direction selection]. Set the parameter
according to the relationships between the servo motor, linear encoder, and rotary encoder.
■
Selection of the encoder pulse count polarity
This servo parameter is used to set the polarity of the load-side encoder to be connected to the CN2L connector to match the
CCW direction of the servo motor and the increasing direction of the load-side encoder feedback. For [Pr. PC27.0 Encoder
pulse count polarity selection], select "0" (load-side encoder pulse increasing direction in the servo motor CCW)" or "1" (load-
side encoder pulse decreasing direction in the servo motor CCW)".
■
A/B/Z-phase input interface encoder Z-phase connection assessment function
This function triggers an alarm by detecting non-signal for Z phase.
The Z-phase connection assessment function is enabled in the initial state. The Z-phase connection assessment function can
be disabled with [Pr. PC27.2 ABZ phase input interface encoder ABZ phase connection assessment function selection].
Select "0" (enabled) or "1" (disabled) for [Pr. PC27.2] as needed.
■
Resolution setting of scale measurement encoder
When using an A/B/Z-phase differential output rotary encoder as a scale measurement encoder, set the resolution in [Pr.
PE51 Load-side encoder resolution setting].
■
Selection of use of A/B/Z-phase differential output type encoder as scale measurement
encoder
If a serial encoder is connected to CN2 and an A/B/Z-phase differential output type encoder is connected to CN2L, determine
which encoder is to be used as a scale measurement encoder. Use [Pr. PC27.5 Scale measurement encoder selection] to
select whether the A/B/Z-phase differential output type encoder is to be used as a servo motor encoder or scale measurement
encoder as required.
No.
Symbol
Name
Outline
PC27.0
**COP9
Encoder pulse count polarity selection
Select a polarity of the load-side encoder.
Initial setting: 0 (load-side encoder pulse increasing direction in the servo motor CCW)
No.
Symbol
Name
Outline
PC27.2
**COP9
ABZ phase input interface encoder
ABZ phase connection assessment
function selection
Select the non-signal detection status for the pulse train signal from the A/B/Z-phase input
interface encoder.
Initial setting: 0 (enabled)
No.
Symbol
Name
Outline
PE51
**EDV2
Load-side encoder resolution setting
Set the resolution of the load-side encoder.
Initial value: 0 [pulse]
No.
Symbol
Name
Outline
PC27.5
**COP9
Scale measurement encoder selection
Select a scale measurement encoder when using an A/B/Z-phase differential output type
encoder.
0: Use an A/B/Z-phase differential output type encoder as a scale measurement encoder.
(Initial value)
1: Use a serial encoder as a scale measurement encoder.
Servo motor
Linear encoder
Address increasing direction of linear encoder
Servo motor in CCW direction