4 APPLICABLE FUNCTIONS
4.13 A/B/Z-phase pulse output function
281
4
Encoder output pulse setting
Set [Pr. PC03.1 Encoder output pulse setting selection]. Set the number of output pulses according to the set value.
■
When [Pr. PC03.2] = "0" (servo motor-side encoder)
Setting value of [Pr. PC03.1]
For servo motors and direct drive motors
For linear servo motors
"0" (output pulse setting)
Set the output pulses per revolution with [Pr. PA15
Encoder output pulses].
Output pulse = Setting value in [Pr. PA15] [pulse/rev]
If [Pr. PC03.2] is set to "1" (load-side encoder), [AL. 037
Parameter error] will occur.
The output pulse setting cannot be used. When "0" is set,
the condition is the same as when "1" is set.
"1" (dividing ratio setting)
Set the dividing ratio to the resolution per servo motor
revolution with [Pr. PA15 Encoder output pulses].
Set the dividing ratio to the travel distance of the linear
servo motor with [Pr. PA15 Encoder output pulses].
"3" (A-phase/B-phase pulse
electronic gear setting)
Set the A-phase/B-phase pulse electronic gear with [Pr.
PA15 Encoder output pulses] and [Pr. PA16 Encoder
output pulses 2].
Set the A-phase/B-phase pulse electronic gear with [Pr.
PA15 Encoder output pulses] and [Pr. PA16 Encoder
output pulses 2].
"4" (A/B-phase pulse through output
setting)
• When a servo amplifier with a firmware version earlier
than B2 is being used
[AL. 037] occurs.
• A/B-phase pulses of the A/B/Z-phase differential output
type encoder are outputted.
• Setting [Pr. PA01.1 Operation mode selection] to "0"
(standard control mode) triggers [AL. 037].
• This is enabled when an A/B/Z-phase differential output
type encoder is used.
When a different encoder is connected, [AL. 037] occurs.
• Output pulse = A/B-phase pulse of A/B/Z-phase
differential output type encoder [pulse]
The setting value in [Pr. PC03.0 Encoder output pulse -
Phase selection] is not applied.
The setting values in [Pr. PA15] and [Pr. PA16] are not
applied.
• When a servo amplifier with firmware version B2 or later
is being used
A/B-phase pulses of the A/B/Z-phase differential output
type encoder are outputted.
• This function is only usable with a direct drive motor.
Setting [Pr. PA01.1 Operation mode selection] to "0"
(standard control mode) triggers [AL. 037].
• This is enabled when an A/B/Z-phase differential output
type encoder is used.
When a different encoder is connected, [AL. 037] occurs.
• Output pulse = A/B-phase pulse of A/B/Z-phase
differential output type encoder [pulse]
The setting value in [Pr. PC03.0 Encoder output pulse -
Phase selection] is not applied.
The setting values in [Pr. PA15] and [Pr. PA16] are not
applied.
Output pulse =
Resolution per revolution
Setting value of [Pr. PA15]
[pulse/rev]
Output pulse =
Travel distance of linear servo motor
Setting value of [Pr. PA15]
[pulse]
Output pulse =
Resolution per revolution ×
Setting value of [Pr. PA16]
Setting value of [Pr. PA15]
[pulse/rev]
Output pulse =
Travel distance of
linear servo motor × Setting value of [Pr. PA16]
Setting value of [Pr. PA15]
[pulse]