Electrical Installation Safety Trainer
AD 1 - MI 3399
52
2.2.3 Exercises
2.2.3.1 Exercise No. 2.2-1: dU, Z
L-N
and I
PSC
measurement on the
supply side
Measuring connection topology
Figure 2-7: Topology in a 1-phase TN system on the supply side
Measuring procedure
1
To measure the line impedance select the line impedance measurement
Z
L-L, L-N
(
Z line
) which measures impedance between phase and neutral conductors.
The line impedance measured at the supply side is actually the reference line
impedance (Z
REF
).
To measure the voltage drop select the voltage drop measurement
dU
.
If the voltage drop is measured at this test point then, the drop should actually be
0,0% since the measured and reference impedances should be the same.
2
To get correct readings during measurement select the appropriate fuse settings
(fuse type, size and trip-out time) by clicking in the bottom left dark grey corner.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...