Electrical Installation Safety Trainer
AD 1 - MI 3399
92
-
Check that loads / consumers are disconnected and/or switched off, surge
protective devices are removed, and lights are switched off.
-
If there are signs of dust and humidity, clean and dry critical parts.
If surge protective devices cannot be removed, than the test voltage could be
reduced to 250 VDC. In this case the insulation resistance limit shall be at least 1
MΩ.
Test individual sub circuits to find the problematic location (by disconnecting of
circu
it breakers, removing fuses…).
2.6.1.1 Insulation resistance of individual circuits / items
Especially during troubleshooting insulation resistance of individual installation parts
are checked. In this case appropriate fuses / switches should be switched OFF in order
to isolate the observed installation part.
Figure 2-35:
Insulation test performed on switchboard and outlet
2.6.2 Exercises
Before running any test check if any RCD is present. If a RCD is present, disconnect
it or it will not be possible to conduct any tests.
2.6.2.1 Exercise No. 2.6-1: R
ISO
in a 1-phase outlet in a TN/TT system
Measuring procedure
1
To measure the insulation resistance select first the
R
ISO
function in the
ISO
section.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...