Other individual resistances can be measured by embracing other electrodes with the
current clamps.
Notes:
Applicable in complex earthing system with numerous parallel earthing electrodes.
Applicable for measuring earthing resistance in transformer stations.
Applicable for measuring lightning systems (Figure 2-57).
Applicable for measuring earthing resistance in TN earthing systems (Figure 2-58).
Especially suitable in urban area.
No disconnection of measured electrodes.
Very fast measurement; no need to place measurement probes and to separate the
measured electrodes.
Very accurate for resistances below 10 Ω.
The minimum distance between driver and sense clamps is at least 30 cm (unless
they are shielded).
Figure 2-57:
Test system (individual earthing rods) with two current clamps
Figure 2-58:
Measurement of resistance to earth of object with two current clamps in TN
system
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...