Within allowed limits and all outlets produce the same result
, then we may
conclude that TN earthing system is being tested.
Loop impedance is much higher than Line impedance (Z
LOOP
>> Z
LINE
):
- If such impedances are present on all measured outlets, then we may conclude
that TT earthing system is being tested.
- If TT earthing system is not present, then there is an error on the PE conductor.
Loop impedance is much lower than Line impedance (Z
LOOP
<< Z
LINE
):
- There is an error on the Neutral conductor.
Maximum allowed Line and Fault loop impedances to ensure the trip-out ability with built-
in fuses type B, C or gL-gG in the installation with nominal mains voltage
U
L-N
= 230 V are
presented in the example table below.
Nominal current of
over-current
protection device (A)
Type of automatic
Fuse B
Type of automatic
Fuse C
Type of
Fuse gG
Ia=5·In
(A)
Zs (
Ω
)
(0,2s)
Ia=5·In
(A)
Zs (
Ω
)
(0,2s)
Ia (A)
Zs (
Ω
)
(0,4s)
2
10
22
20
11
16
13,7
4
20
11
40
5,5
32
6,8
6
30
7,3
60
3,65
47
4,6
10
50
4,4
100
2,2
82
2,6
16
80
2,8
160
1,4
110
2,0
20
100
2,2
200
1,1
147
1,4
Table 1-1: Maximum allowed fault loop impedances in case of used melting fuses
type B, C and gG
3
Fuse trip-out times depend on the characteristics of a built-in fuse or RCD.
Circuit type
Trip-out time
Explosive
100 ms
3-phase
200 ms
1-phase
400 ms
Fixed connection
5 s
Table 1-2: Fuse trip-out times
Where an installation is protected with a RCD, special measuring techniques are used
to avoid tripping out the RCD during the test.
1.4.4 RCD
Installation of RCDs is:
Mandatory in TT systems.
Optional in TN systems, though European countries today typically install RDCs
also on these types of systems.
3
See Metrel’s Handbook
Guide for testing and verification of low voltage installations
for more
parameters/limits.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...