Electrical Installation Safety Trainer
AD 1 - MI 3399
44
-
Trip out Time of RCD in case of fault leakage current flows 5x nominal
differential current of 30mA RCD should be within 40ms.
1.4.6 Insulation
To ensure the complete safety of the installation, one of the main protections against
electroshock of hazardous voltage needs to be tested. The visual inspection is
necessary and the test of insulated parts must be done on each separated circuit.
For this type of testing the installation must be prepared in such a way that
no voltage
is present
and
no loads are connected
. The insulation test starts after the RCD trips
out for that reason.
The insulation test must be done with a voltage higher than possible present line
voltage and the
test voltage must be higher than 500V.
The value of the insulation resistance must be
higher than 1 M
Ω.
1.4.7 Continuity
The basic protection against electroshock of hazardous voltage is ensured by potential
equalizing and earth bonding of all accessible metal parts of the installations in the
surrounding. The visual inspection is necessary and the test of R
LOW
or R
PE
need to be
measured between MPE, remote PE or reference PE points to PE conductors,
conductive parts and housing of connected loads. The test current must be at least
200 mA, AC or DC.
The results should never be higher than
2 Ω
. Recommended results for special
installations are
1 Ω
or lower.
In installations without RCD protection, results must be low enough to ensure trip-out
ability of live installation in case of a fault. The same conditions must be fulfilled as in
the case of fault loop measurement
– referencing to Table 1-1 and Table 1-2.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...