Electrical Installation Safety Trainer
AD 1 - MI 3399
80
trip-out current should be within limits described in chapters RCD trip-out time test and
RCD trip-out current test.
In our case the results we get for all three tests are within the expected limits.
After the trip-out time and trip-out current tests, the RCD is tripped as is the intention
of both test. Be sure to reset the RCD before each test.
Instead, all three mentioned test a predefined RCD
AUTO SEQUENCE
®
test (
RCD
Auto
) can be used. The functionality is that it performs all three test one after another.
The tester is only required to reset the RCD every time it is tripped-out to continue
testing.
Expected results with a simulated error
RCD testing simulated errors do not produce enough contact voltage to properly
display failed results. For this reason no example is given.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...