PAT Appliances & Machines Safety Trainer
AD 3
– MI 3399
244
5.6 Household appliance of class 1
– Coffee machine
Simulates
Error value
Error off Error on
Simulation between contacts
Measurement
taken
Error off Error on
Error 1
Loose contact of PE conductor
Error value
0,02 Ω
0,43 Ω
Earthed metal part (1) and PE pin on
socket (2)
Earth Bond
0,02 Ω
0,43 Ω
Error 2
Insulation fault
Error value
>20 MΩ 106 kΩ
L and PE pins on socket (2)
Insulation 500 V
DC
>20 MΩ 0,106 MΩ
Leakage 230 V,
50/60 Hz
0,00 mA 2,17 mA
Subleakage
0,00 mA 2,17 mA
Error 3
Excessive capacitive current
Error value
/
33 nF
L and PE pins on socket (2)
Insulation 500 V
DC
>100
MΩ
>100 MΩ
Leakage
230V
50/60 Hz
0,00 mA 2,12 mA
Subleakage
0’00 mA 2,12 mA
Error 4
Functional fault
Functional
/
interruptions
Functional
Functional
/
interruptions
Table 5-5: Description of simulated faults / relevant tests
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...