Electrical Installation Safety Trainer
AD 1 - MI 3399
99
2.6.2.4 Exercise No. 2.6-4: R
ISO
varistor measurement
Measuring procedure
1
To measure the insulation resistance select first the
R
ISO
function in the
ISO
section.
2
Set the minimum allowed insulation resistance by clicking in the bottom left dark
grey corner.
3
During this test only cables may be used, where the PE and N cable are connected
together and connected to the GAS pipe above the varistor. The Line cable is
connected to the GAS pipe below the varistor as indicated by the picture below
and Figure 2-39.