Electrical Installation Safety Trainer
AD 1 - MI 3399
47
2.2 Line impedance measurement
Line impedance is measured in a loop comprising of mains voltage source and line
wiring (between the line and neutral conductors or between lines on a 3-phase system).
Scope of the line impedance test is:
To verify effectiveness of installed over current disconnection devices.
To verify internal impedance for supplying purpose.
To verify too high (excessive) internal line impedance for supplying purpose. This
causes too high voltage drop between power transformer and a load.
Figure 2-1: Chart reference for line impedance measurements
Figure 2-2: Measuring Z
Line
in the Application Trainer with the schuko commander
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...