DRIVE FAULTS
92
ERROR/FAULT CODE
PROBABLE CAUSE/ — CORRECTIVE ACTION
901 PCU
IST
FAULT
– Current flow in excess of 300% of rated armature
current detected. Check for:
1. Ground fault or intermittent connection in motor armature circuit.
2. Faulty current measuring module.
3. Poor current regulator tuning.
902
POWER SUPPLY FAULT
(CPU Reset Required)
The Low Voltage Power Supply (A4) output has dropped below 60% of
the rated voltage. This fault will shutdown the drive. Possible causes;
Loss of 115VAC power.
Short circuits in +5V, +/-15V, or +24V circuits, possibly external to the
drive.
Failed Power Supply
Blown fuse internal to power supply.
903 LINE
SYNCRONIZATION
FAULT
(CPU Reset Required)
The Phase Locked Loop has lost synchronization with the 3 Phase AC
input power supply. When this occurs, the Severe Fault flag is set and
the current reference is forced to zero. Generally this is caused by AC
input power problems and is self-correcting. This fault will shutdown
the Drive.
This fault will often occur with a F904 fault.
904
LOW LINE VOLTAGE FAULT
The AC input power has dropped below 80% of the Nominal AC Line
Voltage #9 for 3 consecutive cycles or lower than 50% for one cycle.
When this occurs, the Severe Fault flag is set and the DSD 412 current
reference is forced to zero. This fault will shutdown the Drive.
905
FIELD LOSS FAULT
This fault will shutdown the Drive.
The field current feedback has dropped below 80% of the expected
current during the following conditions:
#49 when Drive is in Field Weakening Mode (Top speed).
#50 when Drive is in Full Field Mode (Accel or Decel).
#53 when Drive is in Standing Field Mode (not running).
Probable causes are:
Open circuit failure of motor field or motor field wiring.
Hardware failure of motor field control circuitry.
Loss of power or incorrect phasing to Field Rectifier.
906 DCU
FAILURE
FAULT
(DSD 412 Power down is required.)
The update of the Dual Port RAM from the Drive Control Unit (DCU) is
unreliable. This requires the replacement of the Drive Control PCB,
A1. This fault will shutdown the drive
.
907 THERMISTOR
FAULT
The thermistor is found to be open or shorted.
Check and/or replace the thermistor. It should measure between 2K –
10K ohms at 20C room temperature. A Thermistor Fault will also
occur if the machine room ambient temperature is below 0C as the
resistance it detected is too high to be measured. An open thermostat
on larger drives will also indicate F907. This fault will not shutdown the
Drive.
Содержание DSD 412
Страница 1: ...DSD 412 DC Elevator Drive Technical Manual CS00407 rev 06...
Страница 6: ...6...
Страница 102: ...MAINTENANCE 102 Figure 24 Connector and E prom Locations...
Страница 103: ...MAINTENANCE 103 Figure 25 Test Point Locations...
Страница 115: ...OUTLINE DRAWING 100A 115 Figure 26 Drive Chassis Outline DSD 412 100 Amp...
Страница 116: ...OUTLINE DRAWING 190A 116 Figure 27 Drive Chassis Outline DSD 412 195 Amp...
Страница 117: ...OUTLINE DRAWING 300A 117 Figure 28 Drive Chasis Outline DSD 412 300 Amp...
Страница 118: ...LAYOUT DRAWING 100A 118 Figure 29 Layout DSD 412 100 Amp A3 A1 A2 A2 L1 NEG GND L2 L3 POS...
Страница 119: ...LAYOUT DRAWING 195A 119 Figure 30 Layout DSD 412 195 Amp A3 A1 A2 A2...
Страница 120: ...LAYOUT DRAWING 300A 120 Figure 31 Layout DSD 412 300 Amp A3 A1 A2 A2...
Страница 121: ......