background image

MAINTENANCE 

 106

Drive Control PCB Replacement. 

1.  Release the front cover of the drive by 

pulling out the four corner fasteners, 
approximately 1/4 inch, until they snap; 
then remove the cover. 

2.  Mark each cable and wire to ensure 

proper reconnection; before 
disconnecting them. 

3.  Disconnect all cables and wires from the 

Drive Control PCB.  Remove nine 
screws holding the  Drive Control PCB 
to the swing out door chassis from the 
front, and remove the Drive Control PCB 
from the power cube. 

4.  If there is an optional circuit board 

attached to the back of the Drive Control 
PCB, disconnect the Local I/O cable 
from J12 on the Drive Control PCB.  
Then remove the mounting screws 
which secure the Local I/O PCB to the 
back of the Drive Control PCB.  Re-
attach the same Local I/O PCB to the 
replacement Drive Control PCB using 
the same hardware in reverse order.  
Re-attach the J12 cable. 

5.  Mount the new Drive Control PCB into 

the power cube by reversing procedure 
in steps 1 through 3.  Be sure to re-use 
the small diameter flat washers under 
the screw heads on the Drive Control 
PCB to maintain proper electrical 
clearances. 

6. 

Remove

 integrated circuits (ICs) U13, 

U14, U39, U40 as appropriate, from the 
defective Drive Control PCB.  Install into 
the same positions on the new board.  
Ensure that polarity notch on IC is 
aligned with the silk screen notch on the 
board.  Each IC is marked with the 
proper “U” number in the bottom left 
hand corner of its label. 

7.  Perform Start-Up Procedure. 

 

IC Replacement 

IMPORTANT 

When replacing any printed circuit board 

(PCB) or any integrated circuit (IC) in the 

DSD drive, proper Electro-static Discharge 

(ESD) procedure MUST be followed. 

EPROM Replacement 

To replace an EPROM (U13, U14, U39, 
U40), first check that the new device has the 

same “U” number on its label as the 
defective device.  Remove the existing 
device and install the replacement in the 
same position.  Then perform the Start-Up 
Procedure in Drive Start . 

 
NVRAM Replacement

 

To replace an NVRAM device (U56), 
remove the defective device and install the 
replacement in the same position.  Then 
perform the Start-Up Procedure.  If you have 
kept a record of the parameter settings you 
should be able to re-load all parameter 
values, save the data and go.  If you do not 
have a record of the working drive 
parameter settings, you must re-enter and 
re-tune all parameters by repeating all drive 
adjustment procedures.

 

 

Testing and Replacement of  Power 
Components. 

Fuse Replacement 

Whenever attaching a fuse, wire or bus bar 
to another component to achieve an 
electrical connection, always apply a thin 
coating of electrically conductive joint 
compound to all contacting surfaces.  
Magnetek recommends using Joint-Al-Z 
compound for all bolted electrical power 
connections. 

Diagnosis of fuses

 — The input AC fuses 

are checked when power is initially applied 
during the Start-Up sequence of the drive, 
and again when a PCU DIAGNOSTICS 
#998 is performed.  The output DC fuse is 
checked only when a PCU DIAGNOSTICS 
#998 is performed. when running, blown 
fuses may cause an F910 or F404.  

With 

input power disconnected

, the fuses may be 

checked with an ohmmeter while still in 
place in the circuit.  Replace any fuse that 
indicates a resistance reading of more than 
a fraction of an ohm.  Re check that the fuse 
is indeed open/blown when removed from 
the circuit.  Be aware that other circuitry may 
cause a low resistance reading to appear 
across a blown fuse.  If there are doubts 
about the fuse being good or bad, remove 
connections to at least one end before 
measurement.  For maximum assurance to 
prevent call-backs, Magnetek recommends 
replacing all three AC line fuses even when 
only one or two are blown. 

Содержание DSD 412

Страница 1: ...DSD 412 DC Elevator Drive Technical Manual CS00407 rev 06...

Страница 2: ...t assume responsibility or accept invoices for unauthorized repairs to its components even though defective The life of the products the Company depends to a large extent upon type of usage thereof an...

Страница 3: ...derations 24 Receipt of Shipment 24 Unpacking Instructions 24 Packing Instructions for Reshipment or Storage 24 Physical Installation 24 Selecting Mounting and Wiring of the Digital Encoder 24 Electri...

Страница 4: ...et Up 67 Field Regulator Set Up 67 AC Input Voltage Requirement Adjustment 67 Speed Regulator Adjustment 67 Drive Faults 88 Function Error Code Listing 88 Troubleshooting 89 Input Output Signal Verifi...

Страница 5: ...pical Power Wiring 29 Figure 7 Typical Analog Signal Wiring 30 Figure 8 Typical Serial Signal Wiring 31 Figure 9 Power Signal Wiring Notes 32 Figure 10 Drive Brake Control Feature 33 Figure 11 Speed S...

Страница 6: ...6...

Страница 7: ...SSOVER RAD 100 1000 500 9 NOMINAL AC INPUT VAC 150 525 230 10 ENCODER PPR P R 600 19999 1024 11 RATED MOTOR RPM RPM 50 0 1999 0 1150 0 12 OVERSPEED 0 0 150 0 110 0 14 V SENSE 0 0 100 0 25 0 15 T SENSE...

Страница 8: ...0 55 FIELD CONTROL AC SOURCE VOLTS VAC 0 525 0 63 U D PICK UP 0 01 100 0 0 10 64 LOW SPEED THRESHOLD 0 1 100 0 2 0 80 OVER SPEED TEST LOGIC 0 1 0 OFF 81 OVER SPEED MULT 1 00 1 50 1 00 82 REFERENCE MU...

Страница 9: ...RROR TRIP TIME SEC 0 20 5 00 5 00 100 SPEED ERROR TRIP LEVEL 0 0 100 0 100 0 101 AUTO FAULT RESET ON LOGIC 0 1 0 OFF 102 3S LOOP FLT LOGIC 0 1 0 OFF 104 SERIAL GAIN SWITCH LOGIC 0 1 0 OFF 105 GAIN SWI...

Страница 10: ...ON 151 PRESET SPEED 1 0 0 1900 0 0 0 152 PRESET SPEED 2 0 0 1900 0 0 0 153 PRESET SPEED 3 0 0 1900 0 0 0 154 PRESET SPEED 4 0 0 1900 0 0 0 155 PRESET SPEED 5 0 0 1900 0 0 0 156 PRESET SPEED 6 0 0 1900...

Страница 11: ...5 00 180 ACCEL 3 S 0 1 100 0 25 0 181 DECEL 3 S 0 1 100 0 25 0 182 INVERT ALARM RELAY LOGIC 0 1 0 OFF 183 K3 LGC OUT SELCT NUM 1 4 1 184 K4 LGC OUT SELCT NUM 1 4 1 185 K5 LGC OUT SELCT NUM 1 4 1 186...

Страница 12: ...19 MEASURED AC LINE VOLTS VAC 620 FIELD TRACKING PU 621 SERIAL COMM ON LOGIC 688 CUBE I D 689 FIELD RANGE FNCT DESCRIPTION UNIT 690 PCU VERSION 404 691 PCU RELEASE 692 DAY 693 MONTH 695 YEAR 696 BETA...

Страница 13: ...E ALARM 407 DCU CEMF ALARM 408 PCU CEMF FAULT 409 PCU RESET FAULT 410 SPEED ERROR TRIP FAULT 411 MAXIMUM AUTO RESETS FAULT FAULT DESCRIPTION 413 FIELD CURRENT TRACKING FAULT 414 SOFTWARE COMPATABILITY...

Страница 14: ...E 932 ARMATURE CEMF VOLTAGE IN XCESS DURING SELFTUNE 933 IARM DOES NOT INCREASE TO NEAR TEST AMPS DURING SELFTUNE FAULT DESCRIPTION 934 CALC ARML IS UNDER RANGE DURING SELFTUNE 935 VOLTAGE FEEDBACK AN...

Страница 15: ...one of four chassis sizes Refer to the outline dimension drawings furnished in section 6 Each power cube is designed for mounting inside a qualified electrical enclosure Space allowances for air circ...

Страница 16: ...ONENTS L1 L2 L3 LPR LOOP PICK UP RELAY K1 CONTACTOR PILOT RELAY MOTOR TRANSFORMER THERMOSTATS E STOP SENSE K1 SAFETY CHAIN LPR ME LOOP CONTACTOR CONTROL POWER XFMR POWER SUPPLY PCB HEAT SINK COOLING F...

Страница 17: ...CAL CDU STATUS LEDS 18888 UN PROT NV MEM MEM PROT SWITCH RE SET POWER CONVERSION UNIT MICROPROCESSOR DUAL PORT MEMORY RAM EPROMS NV RAM RAM EPROMS DRIVE CONTROL UNIT MICROPROCESSOR IN OUT DRIVERS TB1...

Страница 18: ...nt View Q7 FIELD SCR SCR S A2TB5 SNUBBER PCB AC INPUT FOR FIELD SUPPLY DC OUTPUT FIELD SUPPLY ARMATURE CURRENT TRANSDUCE R DC ARMATURE FUSE F4 AC LINES FUSES F1 3 INPUT POWER LUGS GROUND LUG ARMATURE...

Страница 19: ...INTRODUCTION 19 Figure 4 Component Layout Right Side View POWER SUPPLY COVER A4 POWER SUPPLY A4 TB3 A1 MAIN CONTROL PCB...

Страница 20: ...the field rectifier SCRs A separate current measuring device is used to monitor the DC current flowing to the motor field Additional connections allow for a separate step up or step down transformer t...

Страница 21: ...Motorola 68000 microprocessor Random Access Memory RAM provides memory space to store values that are maintained only while power is on Non Volatile Random Access Memory NVRAM maintains drive control...

Страница 22: ...and a row of four push buttons The DATA and DATA PEND LEDs are used to indicate the significance of the LED display data and the four push buttons DATA FCTN UP DOWN and are used to operate the SCDU T...

Страница 23: ...of conditions that MUST BE OBSERVED to prevent personal injury death or serious equipment damage How To Contact Magnetek For additional information contact any Magnetek Representative or contact the...

Страница 24: ...well ventilated Maintenance will be minimized if the drive is located in a clean atmosphere The standard drive is designed for vertical mounting Attach the drive to a cabinet panel or other vertical...

Страница 25: ...mounting and holding the rubber wheel against the sheave 2 Lack of concentricity of the measuring wheel 3 The rubber wheel can develop a flat spot when it sits idle for an extended time This goes away...

Страница 26: ...b panel on which the DSD 412 drive is mounted to the common grounding stud Other electrical equipment such as fans or relay circuits may be grounded to the electrical sub panel A grounding wire should...

Страница 27: ...phase power fuses see section describing standard control display unit operation for more detailed information about this test 3 If the FAULT LED lights and a fault code appears on the SCDU then refer...

Страница 28: ...Set the NV RAM PROTECT switch to the protect position UN PROT NV RAM light is off to ensure that set up data cannot be corrupted 6 Operate drive using external control signal inputs shown on the Inter...

Страница 29: ...INTERCONNECT DRAWING 29 Figure 6 Typical Power Wiring 3 PH DRIVE ISOLATION TRANSFORMER AS REQ D TB1 82 24VDC TB1 78 K4...

Страница 30: ...CDU PORT DATA FLOW ALARM RELAY MAY BE ENERGIZED OR DE ENERGIZED ON ALARMS SEE TECH MANUAL FUNCTION 182 INPUT OUTPUT CONNECTIONS USING ANALOG INTERFACE MODEL NUMBER 53STXXXX 3X00 DRIVE OK NO FAULTS REL...

Страница 31: ...al Signal Wiring ALARM RELAY MAY BE ENERGIZED OR DE ENERGIZED ON ALARMS SEE TECH MANUAL FUNCTION 182 DRIVE OK NO FAULTS RELAY ENERGIZED WHEN NO FAULTS ARE PRESENT J1 DB9 CONNECTION RS422 DATA FLOW PRO...

Страница 32: ...FROM L1 AND L2 IF A DIFFERENT VOLTAGE IS REQUIRED MOVE THE ORIGINAL WIRES FROM AC1 AND AC2 TO L1A AND L2A THE ALTERNATE SUPPLY SHOULD THEN BE BROUGHT INTO AC1 AND AC2 THIS CONNECTION IS PHASE SENSITIV...

Страница 33: ...R C 115 VAC CONTROL POWER K3x K6x BRAKE PICK BRAKE LIFT ELEVATOR BRAKE COIL R HOLD BRAKE PICK BRAKE VAC SUPPLY SOURCE BRAKE LIFT CONNECTIONS FOR ELEVATOR BRAKE CONTROL RECTIFIER AS REQ D BRAKE LIFT R...

Страница 34: ...ut Wiring 52 54 12 53 11 S4 S3 S2 S1 48 S0 24V 52 54 12 53 11 S4 S3 S2 S1 48 S0 24V ALTERNATE METHODS TO ACHIEVE PROGRESSIVE SPEED SELECT LOGIC OR PROGRESSIVELY SCANNED RELAY LOGIC USING DIODES 1N4003...

Страница 35: ...s of the NVRAM P r o t If the display shows Prot it is necessary to move the NV RAM PROTECT switch to the OFF position and press the CPU RESET button in order to load defaults into NVRAM and restart t...

Страница 36: ...between the Data level and the Function level Press the DATA FCTN key when the desired function number is in the display At this point the SCDU leaves the Function level and enters the Data level Not...

Страница 37: ...eeded the display will change to the appropriate limit and the green LED will light 5 Press the DATA FCTN key to put the SCDU back into the Function level As with the example above the SCDU display wi...

Страница 38: ...er or not the drive stops or continues to run is dependent on the way the particular fault is implemented Most standard faults are set up so that the drive will stop if a fault occurs Faults stored on...

Страница 39: ...n the Fault List In this case the SCDU display is E 1 F 0 Red LED Lit 5 Press either the or key repeatedly to change the numbers after the E and F from 1 to 0 and vice versa Starting from no declarati...

Страница 40: ...n on the SCDU display and optionally cleared IMPORTANT The process of clearing a fault from the Fault List DOES NOT actually clear the condition that caused the fault To view the first fault on the li...

Страница 41: ...parameter list Function 994 is used to perform the transfer of data between the NVRAM and active parameter lists The process for copying data to or from the NVRAM parameter list is as follows 1 Use th...

Страница 42: ...EDs Off 2 Press the DATA FCTN key to enter the Data level for function 995 The green LED is now lit to indicate that this function is currently being accessed The SCDU will now display L O A d Green L...

Страница 43: ...to indicate that this function is currently being accessed The SCDU displays the word Prot if the NV RAM PROTECTION switch is in the position that will not allow any updates to the NVRAM P r o t If t...

Страница 44: ...lt Codes F910 Blown Fuse F911 Shorted SCR F912 Open SCR and F917 Reverse Armature Feedback Wires will not appear on the SCDU if the Error Disposition List is programmed so that they are not reported t...

Страница 45: ...s one or more Open AC Fuses it displays the fault code for a blown fuse F910 F 9 1 0 Both LEDs Off If the PCU detects one or more shorted SCR doubler packs the SCDU displays the fault code for a short...

Страница 46: ...ons Analog speed reference zero adjustment Alarm Relay to indicate important but non critical conditions Motor or transformer thermostat over temperature Motor Over Load Drive Over Heating Low Utility...

Страница 47: ...logic for redundant safety This operating mode is selected by setting 110 to 3 The speed sensitivity of the serial velocity reference may be adjusted using function 82 Maintainance mode Armature Volta...

Страница 48: ...80 turns the effect of that multiplier on and off However be aware that the Drive Over Speed trip fault F97 set by function 12 is a fixed percent of rated rpm and will also be tested and indeed shoul...

Страница 49: ...This value is used to calculate armature current regulator gains and to calculate motor CEMF Function 6 Armature Inductance Units HNY Range 0 001 1 0000 Default 0 01 This is the value of the motor cir...

Страница 50: ...ange 0 0 100 0 Default 5 0 This entry sets the percentage of tach feedback below which a tach loss will be declared But this alone will not result in a tach loss fault being declared Thus a tach loss...

Страница 51: ...lt 6 0 This entry sets the closed loop bandwidth response of the velocity regulator at speeds above the setpoint identified in 105 The tracking delay between the speed dictation ramp and the actual mo...

Страница 52: ...Full field amps function 50 It is used to calculate motor field circuit resistance and determine motor field current regulator gains Improper adjustment can affect stability Function 53 Standby Field...

Страница 53: ...rence of 10V when function 82 is set to 1 000 and function 80 is OFF Function 83 Motor Ovld Tout Units SEC Range 2 0 500 0 Default 48 0 This value shapes the motor overload time out curve Function 84...

Страница 54: ...Timer Units SEC Range 0 1 5 0 Seconds Default 2 0 Used only when elevator brake control is engaged Establishes a limit on how long the drive may continue to run after the Run command logic line is rel...

Страница 55: ...Units Range 0 0 100 0 Default 100 0 This value sets the magnitude sensitivity of the Speed Error Trip detection function Speed errors larger than function 100 for longer than function 99 seconds will...

Страница 56: ...n 150 for speed selects Setting this value to 3 enables serial link control of the velocity reference and external ramp slew limits rates of function 21 Setting this value to 4 enables a uni polar ana...

Страница 57: ...ut not both Function 116 Decel Rate Latch Units logic Range 0 Off 1 On Default 0 Off When set this control bit causes the decel ramp rate active at the start of decel to remain in effect until the dec...

Страница 58: ...ed in function 17 If feet per minute is used at function 17 then the units for function 151through 157 shall also be feet per minute No value for function 151through 157 should be larger than that for...

Страница 59: ...on 1 A percent S of 0 1 corresponds to almost all linear acceleration A percent S of 100 will make the S curve 1 smooth with no linear acceleration portion Effective only when internal pre set speeds...

Страница 60: ...portion of the timed ramp curve during ramped deceleration 3 A percent S of 0 1 corresponds to almost all linear deceleration A percent S of 100 will make the S curve 1 smooth with no linear decelerat...

Страница 61: ...in S Figure 14 S Curve with 100 S LINEAR ACCEL REGION LINEAR DECEL REGION CONTROLLED ACCEL JERK OR S CONTROLLED DECEL JERK OR S CONTROLLED ACCEL JERK OR S PORTION CONTROLLED DECEL JERK OR S PORTION 17...

Страница 62: ...May be used as an indication that the drive is in control and that the elevator brake may be released D Moving Up Output becomes active when encoder velocity is greater than the setting of function 6...

Страница 63: ...6 37 A F C N Output K4 Controlled by Function 184 Open Collector Type A1TB1 78 B A G P Output K5 Controlled by Function 185 Open Collector Type A1TB1 79 C G H I Output K6 Controlled by Function 186 Op...

Страница 64: ...3 Pre Torque Input Units This display is the pre torque reference as applied to starting the velocity regulator The value is latched to display the pre torque value used at the start of a run Prior to...

Страница 65: ...g level Units PU This is the difference between the Field Current reference and the Feedback F413 warning will result if higher than F192 for 5 seconds Function 621 Serial Communication Control Enable...

Страница 66: ...200 600 47 300 600 48 400 600 49 600 600 50 800 600 This number should agree with the DSD 412 drive data nameplate Table 9 Cube I D Number FIELD CURRENT RANGE 2 200HP Indicates actual SW1 setting 689...

Страница 67: ...at top speed before attempting to set Per Unit Inertia Note If Field Current is set too low the necessary motor torque may not be available resulting in excessive motor armature current or current li...

Страница 68: ...ope resonance See Table 8 Tuning E REG The basic concept and purpose of E Reg is to have a relatively low closed encoder loop bandwidth to prevent amplification of natural rope oscillations but to fee...

Страница 69: ...ycle to compensate for the tracking delay Setting the Speed Bandwidth to a high value in order to compensate for a poor Per Unit Inertia setting is an improper adjustment There may be some minor inter...

Страница 70: ...Figure 16 E REG Tracking Profiles 2 S P E E D 0 TIME ACCEL TIME ZERO SPEED Velocity Reference Speed Feedback with Bandwidth 40 set to 5 radians 200 mSec tracking delay Speed Feedback with Bandwidth 40...

Страница 71: ...ng Per Unit Inertia Setting TOO HIGH Velocity Under Shoot Figure 17 E REG Tracking Profiles 3 S P E E D 0 TIME ACCEL TIME ZERO SPEED Velocity Reference RATED SPEED Speed Feedback with Per Unit Inertia...

Страница 72: ...position overshoot of floor landings and potentially repetitive speed oscillations or speed hunting If these symptoms occur back off on the Notch Depth setting 190 and or reduce the setting of 191 Not...

Страница 73: ...ion causes false detections Verify by test that empty car down or full payload weight up will not cause nuisance trips Start Stop Timing A typical elevator run sequence is shown in Figure 19 Elevator...

Страница 74: ...VATOR VELOCITY ZERO OTHER MOTOR ARMATURE CURRENT FULL STAND BY MOTOR FIELD CURRENT MUST REMAIN VALID DURING ENTIRE RUN ZERO SPEED SPEED DIRECTION RAMP CMDS 0 1 CONTACTOR ACK LPR CONTACTOR 0 1 0 0 1 HA...

Страница 75: ...hile drive is running F405 fault will result Safety chain may remain closed 7 Open Drive Field Enable if desired Will cause field current to go to stand by idle value May remain active if drive will b...

Страница 76: ...or 6 NOTE Always set all other unused pre set speeds to zero Table 11 Binary Input Control Example With 150 Off 112 On S4 S3 S2 S1 S0 Pre set Use 0 0 0 0 0 none Zero Speed select 0 0 0 0 1 1 Inspecti...

Страница 77: ...must be at least that far away from the beginning of the run The single floor target running speed and or accel decel times must be adjusted to meet the above criteria conditions or the landing may be...

Страница 78: ...captured and latched each time the drive is started by closure of the motor dc loop contactor in response to activating the Run command That value will be used to pre load the speed error integrator...

Страница 79: ...CAR CONTROLLER PLC Differential Input Circuit Common Vnoise TB1 68 63 66 70 com 69 shld 44 OR 43 TB11 GND Twisted Shielded N C at PLC end Proper connections Noise current does not flow through signal...

Страница 80: ...he host B1 1 to act as a synchronization bit for incoming messages from the host B2 0 Stop requested 1 Run requested B3 0 No request to clear faults 1 Clear fault requested B4 0 Demand Velocity is not...

Страница 81: ...e contains 8 logic signals to indicate drive faults B0 0 No Motor over load 1 Motor over load fault F400 B1 0 No excessive field current 1 Excessive field current F401 B2 0 No contactor failure 1 Cont...

Страница 82: ...display is 2 rows of 16 characters Therefore an update of an entire screen would require several packets Byte 11 This byte contains the calculated checksum of the data within this packet It is the mod...

Страница 83: ...egulator is switched to be E Reg to precisely track follow the velocity reference profile Be aware that this anti rollback feature works from encoder tachometer signals So there must and will be some...

Страница 84: ...e the initial movement should be downward Then repeat floor runs as in 5 with a full load Ride the car to verify smoothness Adjustment procedure is complete ARB Adjustment Hints And Cautions 1 Caution...

Страница 85: ...through the brake to start the car is a result of poor velocity reference release Vs brake release timing With ARB the velocity reference should not be released to move away from zero until after the...

Страница 86: ...perate a primary power contactor 115 VAC control power to the drive must remain ON for this feature to be operative Refer to installation diagrams supplied in Section 2 at Figure s 2 1 for all suggest...

Страница 87: ...brake drops as set by the Brake Drop Timer 90 4 When the Brake Drop Timer expires motor armature current ramp down will occur as set by 85 This will gradually transfer torque from motor to brake to he...

Страница 88: ...LT 403 5 MIN FULL FIELD FAULT 404 OPEN ARMATURE CIRCUIT FAULT 405 SAFETY CIRCUIT FAULT 406 10 LOW LINE ALARM 407 EXCESSIVE DCU CEMF ALARM 408 EXCESSIVE PCU CEMF FAULT 409 UNEXPECTED PCU RESET 410 SPEE...

Страница 89: ...2 drive See 102 Causes Defective Loop Contactor Aux Check for proper feedback at TB1 7 Defective Contactor Check for open coil or mechanical binding Defective Pilot Relay LPR Interference from other e...

Страница 90: ...xpectedly reset Verify that correct PCU software and revision level is being used Possible problem with main circuit card hardware Look for external noise interference Ensure that equipment and signal...

Страница 91: ...tor tuning Check 40 41 42 Velocity reference set above rated speed Intermittent velocity encoder 98 TACH LOSS FAULT The drive does not see the encoder velocity in proportion to armature voltage indica...

Страница 92: ...ecutive cycles or lower than 50 for one cycle When this occurs the Severe Fault flag is set and the DSD 412 current reference is forced to zero This fault will shutdown the Drive 905 FIELD LOSS FAULT...

Страница 93: ...agnostics function Detection is accomplished by measurements via voltage dividers on the Armature Interface PCB A2 Possible causes are One or more of AC input fuses are blown Power wiring problem chec...

Страница 94: ...ed properly Missing or wrong Cube ID PCB Wrong PCU software in U13 14 Faulty Armature Interface PCB replace PCB Faulty Drive Control PCB replace PCB 923 LOAD CURRENT SETTING FAULT DSD power down is re...

Страница 95: ...Prot CORRUPTED NVRAM DATA The NVRAM has lost parameter set up data This fault will occur if the battery within NVRAM chip U56 is weak The drive display will show Prot if a loss of data is detected wh...

Страница 96: ...pen circuit voltage to motor armature circuit Measured armature voltage is greater than 10 of rated volts 7 Probable Causes Motor is rotating producing CEMF Unbalanced SCR leakage with low voltage set...

Страница 97: ...s circuit Probable Causes Missing wire to bus voltage feedback Discrete wires on drives larger than 300 amps DC Component problem Feedback voltage divider ratio does not match that identified in Cube...

Страница 98: ...ALL FUSES TEST GOOD WITH OHMMETER Control power applied before 3 phase armature supply Short circuit in 15 V wiring circuits prevents analog circuit measurements from working Verify that 3 phase power...

Страница 99: ...r application Function 981 does not work with the Portable Control display Unit Here s how to use this valuable troubleshooting tool 1 Press the Up or Down keys and go to F 981 2 Press the DATA FCTN K...

Страница 100: ...ce Some of the probable causes in Table 13 Fault Code Descriptions mention problems at connectors all of which are on the Drive Control PCB Table 14 Connector Definitions describes the basic function...

Страница 101: ...he Drive Control PCB from the DSD 412 Power Supply PCB J13 10 Pin Header Provides power supply and board sensing connections to the DSD401 Signal Interface PCB A3 This cable is the same as that used t...

Страница 102: ...MAINTENANCE 102 Figure 24 Connector and E prom Locations...

Страница 103: ...MAINTENANCE 103 Figure 25 Test Point Locations...

Страница 104: ...G HI DCU C SCAN IS RUNNING HI DCU D SCAN IS RUNNING TP13 TP14 LAN E O Chip select for LAN mode High Active EVEN ODD Address Select High 5V TP15 TP16 TP17 F SCAN TIME E SCAN TIME ABCDE SCAN TIME HI DCU...

Страница 105: ...up Noise will cause erratic Drive operation See TP39 TP38 ANALOG TACH FEEDBACK ANALOG TACH SIGNAL When used TP39 ARMATURE CURRENT FEEDBACK Filtered Armature Current Feedback Signal Average of Armatur...

Страница 106: ...the new device has the same U number on its label as the defective device Remove the existing device and install the replacement in the same position Then perform the Start Up Procedure in Drive Start...

Страница 107: ...onents of the DSD 412 for control of motor field consist of the A3 PCB and associated SCR Rectifier module Q7 located under the PCB Input power is single phase voltage supplied to A3TB1 terminals AC1...

Страница 108: ...l unit 5 Replace the Armature Interface PCB in reverse order of disassembly Torque mounting screws down to 20 inch pounds SCR Testing and Replacement 1 Using a multimeter on the X100 range press the p...

Страница 109: ...ternately turn at a time Continue with this procedure until the Belleville washers become flat An abrupt change in torque will be detected when the Belleville becomes flat 9 Reinstall the AC and DC bu...

Страница 110: ...s can and should be done before any disassembly or removal of the SCR Power Bridge Ohmmeter SCR Testing 1 Using a multi meter on the X100 range press the positive probe to the positive right side DC b...

Страница 111: ...es at TB5 3 Remove 12 pairs of the plug on SCR gate and cathode leads 4 Remove the 3 phase connection nuts at E31 E32 E33 near middle of the PCB Do not remove the threaded stud 5 Remove the 6 large nu...

Страница 112: ...chassis from the top side the reverse of 1 e above c Align the transducer module mounting holes with those in the chassis Start all 4 chassis mounting screws and then tighten them to 10 inch pounds d...

Страница 113: ...Assembly Thermostat 25A 50A 100A 195A 300A ALL 300A U1 U1 U1 U1 U1 RT1 S1 S2 LA05P00217 0015 LA05P00217 0014 LA05P00217 0042 LA05P00645 0018 LA05P00217 0020 46S03596 0050 46S03596 0060 1 1 1 1 1 1 2 D...

Страница 114: ...tion female All Connects to TB3 of Power Supply A4 05P00060 0373 1 Cable 115 VAC Cooling Fan with Plug ALL Connects 115 Vac to fan Required for DSPR option addition 05P00016 0045 1 PCDU Hand held Serv...

Страница 115: ...OUTLINE DRAWING 100A 115 Figure 26 Drive Chassis Outline DSD 412 100 Amp...

Страница 116: ...OUTLINE DRAWING 190A 116 Figure 27 Drive Chassis Outline DSD 412 195 Amp...

Страница 117: ...OUTLINE DRAWING 300A 117 Figure 28 Drive Chasis Outline DSD 412 300 Amp...

Страница 118: ...LAYOUT DRAWING 100A 118 Figure 29 Layout DSD 412 100 Amp A3 A1 A2 A2 L1 NEG GND L2 L3 POS...

Страница 119: ...LAYOUT DRAWING 195A 119 Figure 30 Layout DSD 412 195 Amp A3 A1 A2 A2...

Страница 120: ...LAYOUT DRAWING 300A 120 Figure 31 Layout DSD 412 300 Amp A3 A1 A2 A2...

Страница 121: ......

Страница 122: ...Elevator Products N136 W4863 Campbell Drive Menomonee Falls Wisconsin 53051 800 236 1705 262 252 6999 FAX 262 790 4142 http www elevatordrives com Magnetek Elevator Products Europe 20 Drake Mews Crown...

Отзывы: