Lucent Technologies Lineage
®
2000 100A Ferroresonant Rectifier J85503A-1
Issue 6 October 1998
Testing 6 - 21
percent rated load until they carry less than 95 percent
rated load.
d. Repeat from Step 2 (battery voltage check and
adjustment) until all rectifiers are carrying between 5
and 95 percent rated load and the battery voltage is
within the required tolerance of the desired float
voltage.
e. Turn on one of the spare rectifiers, and turn off one of
the previously loaded rectifiers (same number of
rectifiers on).
f.
Repeat Steps b through d for each rectifier that has not
be adjusted.
g. Upon completion, turn all rectifiers on.