Lucent Technologies Lineage
®
2000 100A Ferroresonant Rectifier J85503A-1
4 - 2 Safety
Issue 6 October 1998
and/or local codes. The size of the overcurrent
protector used must not exceed 50A. Refer to the
equipment ratings to assure rating of equipment will
not exceed 80% of the value of the protector chosen.
–
An accessible ac disconnect/protection device to
remove ac power from the equipment in the event of
an emergency must be provided.
–
For installations in the United States, UL-listed
compression connectors should be used to terminate
UL-listed field-wired conductors where required.
For all installations, the appropriate connector
should be applied only to the correct size conductor
as specified by the connector manufacturer using
only the connector manufacturer's recommended
tooling or tooling approved for that connector.
–
If the proper connector for the country of installation
is not provided, obtain appropriate connectors and
follow manufacturer’s and all local requirements for
proper connections. All national and local rules and
regulations are to be followed when making field
connections.
–
Torque electrical connections to the values specified
on labels or in the product documentation.
Precautions
When working on or using this type of equipment, follow these
precautions:
–
This unit must be installed, serviced, and operated
only by skilled and qualified personnel who have the
necessary knowledge and practical experience with
electrical equipment and who understand the
hazards that can arise when working on this type of
equipment.
–
Because of the hazardous voltages supplied to and
within the equipment, make sure the equipment, all
associated framework, and the cable rack are
properly grounded per local job instructions before
turning on any power to the rectifier.
–
For equipment connected to batteries, disconnecting
the AC alone will not necessarily remove power to
the equipment. Make sure the equipment is not also
powered by the batteries or the batteries are not
connected to the output of the equipment.
–
AC voltage may be present in the unit even when the
Power switch is in the Off position.