Lucent Technologies Lineage
®
2000 100A Ferroresonant Rectifier J85503A-1
8 - 4 Spare Parts and Replacement Procedures
Issue 6 October 1998
Spare Fuses
Table 8-C provides spare fuse information for the J85503A-1
rectifier. A commercial equivalent fuse and the appropriate SD
sheets are referenced.
Replacing
Circuit Modules
This section gives step-by-step instructions for replacing circuit
modules CM1, CM2, and CM3.
Replace CM1
Option Board
1. Turn the rectifier Power switch Off.
2. Turn the rectifier DC Output circuit breaker off (down).
3. At the ac service panel supplying power to the rectifier,
remove the input fuse assigned to the rectifier, or turn the
circuit breaker Off.
Table 8-C: Spare Fuse Information
Fuse
Designation in
SD Drawing
Lucent Part
Code
Rating
(Amperes)
Commercial*
Equivalent
Shown on SD
Sheets
F1
KS-19780, L6
30
SOC‡ Type
SKM4
B1, C4
F2
F3
FA1
70G
1/2
BUSSMAN†
70G
FA2
FA3
FA5 (–V)
70G
1/2
BUSSMAN†
70G
B1, C1
FA6 (+V)
* Or other suitable commercial equivalent.
† BUSSMAN is a trademark of the BUSSMAN Company.
‡ SOC is a trademark of SAN-O Industrial Corporation.
Caution
Follow instructions above under “Handling Circuit Modules”
to minimize electrostatic discharge when handling circuit
modules.
Do not connect or disconnect circuit modules with voltages
present or equipment damage may occur.