Lucent Technologies Lineage
®
2000 100A Ferroresonant Rectifier J85503A-1
Issue 6 October 1998
Installation 5 - 19
6. Turn the DC Output circuit breaker on (up).
7. Adjust the Output Volts Adj potentiometer to obtain the
desired initial charge voltage within the limits specified in
the preceding caution.
8. After completing the initial charge, turn the rectifier
Power switch Off and the DC Output circuit breaker off
(down).
9. Replace option straps K and M on the CM1 option board.
10. Turn the Output Volts Adj potentiometer fully
counterclockwise.
11. To restore the rectifier to service, follow the procedure in
Section 7, Troubleshooting and Adjustments.
Caution
In the following step, DO NOT set the rectifier output voltage
to exceed 62 volts (48-volt rectifier) or 31 volts (24-volt
rectifier) or damage to the unit may result.