78
WWW.LCMETER.COM
LCI40
Series IOM
6 oPeration
6.5.13 diagnosis Messages
(Menu C1.5.7 to .C1.5.14)
These settings make it possible to change the status
signal of the respective diagnosis message (status
group).
6.5.14 optical Keys (C6.2.4)
This function can deactivate the optical keys. In the
display, the switched off state of the optical keys is
represented by a lock 1.
In this case, the device may only be operated using the
push buttons.
6.5.15 Graphic Page (Menu C6.5)
With this converter, the trend of the main measurement
can be graphically displayed. The first measurement
on display page 1 is always defined as the main
measurement.
•
Menu C6.5.1 defines the range for the trend indicator
(manual or automatic).
•
Menu C6.5.2 defines the range for manual setting.
•
Menu C6.5.3 defines the time span for the trend
indicator.
6.5 description of Functions
6.5.16 Save Settings (Menu C6.6.2)
This function allows all settings to be stored in a
memory.
•
Backup 1: Saves settings in backup memory area 1
•
Backup 2: Saves settings in backup memory area 2
6.5.17 load Settings (Menu C6.6.3)
This function allows the complete stored settings to be
loaded again.
•
Backup 1: Loading from backup - memory 1
•
Backup 2: Loading from backup - memory 2
•
Factory: Uploading the original factory settings
6.5.18 Passwords (Menu 6.6.4 Quick Set;
Menu 6.6.5 Setup)
To create a password for the Quick Set menu or Setup
menu, you must enter a 4-digit code into the menu.
You are then prompted for this password every time
changes are to be made to the corresponding menus.
There is a hierarchy. The Setup password can also be
used to perform changes in the Quick Setup menu.
Enter 0000 in each menu to disable the password.
6.5.19 date and time (C6.6.6)
The signal converter has a real time clock which is used
for all of the log functions in the device.
This function can be used to set the date and time of
the real time clock.
6.5.20 Quick access (C6.6.7)
In measuring mode, pressing the ^ key for 2.5 seconds
carries out the “Quick Access” function.
Totalizers 1, 2, 3 and All Totalizers can be reset.