8 teChniCal data
Pulse or Frequency Output
Passive
U
ext
≤
32 VDC
-
f
max
in operating menu set to f
max
≤
100 Hz:
I
≤
100 mA
open:
I
≤
0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at I
≤
10 mA
U
0, max
= 2 V at I
≤
1 00 mA
f
max
in operating menu set to 100 Hz <
fmax
≤
10 kHz:
I
≤
20 mA
open:
I
≤
0.05 mA at U
ext
= 32VDC
closed:
U
0, max
= 1.5 V at I
≤
1mA
U
0, max
= 2.5V at I
≤
10 mA
U
0, max
= 5.0V at I
≤
20 mA
Low Flow Cut Off
Function
Switching point and hysteresis separately adjustable for each output, counter and the display
Switching Point
Set in increments of 0.1%.
0 to 20% (current output, frequency output)
Hysteresis
Set in increments of 0.1%.
0 to 5% (current output, frequency output)
Time Constant
Function
The time constant corresponds to the elapsed time until 67% of the end value has been
reached according to a step function.
Settings
Set in increments of 0.1s.
0 to 100 s
8.2 technical data