105
WWW.LCMETER.COM
LCI40
Series IOM
8 teChniCal data
8.2 technical data
PROFIBUS DP
Description
Galvanically isolated acc. to IEC 61158
Profile version: 3.02
Automatic data transmission rate recognition (max. 12 MBaud)
Bus address adjustable via local display at the measuring device
Function Blocks
8 x analogue input, 3 x Totalizer
Output Data
Mass flow, volume flow, mass counter 1 + 2, volume counter, product temperature,
several concentration measurements and diagnostic data
PROFIBUS PA
Description
Galvanically isolated acc. to IEC 61158
Profile version: 3.02
Current consumption: 10.5 mA
Permissible bus voltage: 9 - 32 V; in Ex application: 9 - 24 V
Bus interface with integrated reverse polarity protection
Typical error current FDE (Fault Disconnection Electronic): 4.3 mA
Bus address adjustable via local display at the measuring device
Function Blocks
8 x analogue input, 3 x Totalizer
Output Data
Mass flow, volume flow, mass counter 1 + 2, volume counter, product temperature,
several concentration measurements and diagnostic data
FOUNDATION Fieldbus
Description
Galvanically isolated acc. to IEC 61158
Current consumption: 10.5 mA
Permissible bus voltage: 9 - 32 V; in Ex application: 9 to 24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.01
Function Blocks
6 x analogue input, 3 x integrator, 1 x PID
Output Data
Mass flow, volume flow, density, temperature of tube, several concentration
measurements and diagnostic data
Modbus
Description
Modbus RTU, Master / Slave, RS485
Address range 1 to 247
Supported function codes 01, 03, 04, 05, 08, 16, 43
Baudrate 1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600, 115200 Baud