103
WWW.LCMETER.COM
LCI40
Series IOM
8 teChniCal data
Status Output / Limit Switch
Function and Settings
Adjustable as automatic measuring range conversion, display of flow direction, overflow, error,
switching point
Valve control with activated dosing function
Status and/or control: ON or OFF
Operating Data
Basic I/Os
Modular I/Os
Ex i
Active
-
U
int
= 24 VDC
I
≤
20 mA
open:
I
≤
0.05 mA
closed:
U
0, nom
= 24 Vat I = 20 mA
-
Passive
U
ext
≤
32 VDC
I
≤
100 mA
open:
I
≤
0.05 mA at
U
ext
= 2VDC
closed:
U
0, max
= 0.2 Vat I
≤
10 mA
U
0, max
= 2 Vat I
≤
100 mA
U
ext
≤
32 VDC
I
≤
100 mA
R
L
, max = 47 k
Ω
R
L
, min=(Uext-U0)/Imax
open:
I
≤
0.05 mAat U
ext
= 32VDC
closed:
U
0, max
= 0.2 Vat I
≤
10 mA
U
0, max
= 2 Vat I
≤
100 mA
-
8.2 technical data