58
WWW.LCMETER.COM
LCI40
Series IOM
6 oPeration
6.4 Function tables
6.4.3 Menu C, Setup, continued
No.
Function
Settings / Descriptions
C3._ Status Output X
C3._
Status Output X
X (Y) stands for one of the connection terminals A, B, C or D _ stands for Fct. C3.2 (A) /
C3.3 (B) / C3.4 (C) / C3.5 (D)
C3._.1
Mode
The output shows the following measuring conditions:
Failure (output set, signals status of the category “Failure” refer to Status messages and
diagnostic information on page 104) /
Out Of Specification (output set, signals status of category “Failure” or “Maintenance
Required” or “Out Of Specification” refer to Status messages and diagnostic information on
page 104) /
Maintenance Required (output set, signals status of category “Failure” or “Maintenance
Required” refer to Status messages and diagnostic information on page 104) /
Flow Polarity (polarity of the current flow) /
Flow Over Range (over range of the flow)
Totalizer 1 Preset (activates when Totalizer X preset value is reached) /
Totalizer 2 Preset (activates when Totalizer X preset value is reached) /
Totalizer 3 Preset (activates when Totalizer X preset value is reached) /
Output A (activated by the status of output Y, additional output data see below) /
Output B (activated by the status of output Y, additional output data see below) /
Output C (activated by the status of output Y, additional output data see below) /
Output D (activated by the status of output Y, additional output data see below) /
Off (switched off)
C3._.2
Current Output Y
Only appears if output A to C is set under “Mode” (see above), and this output is a “Current
Output”.
Polarity (is signalled)
Over Range (is signalled)
Automatic Range signals lower range
C3._.2
Frequency Output Y
and Pulse Output Y
Only appears if output A, B or D is set under “Mode” (see above), and this output is a
“Frequency/Pulse Output”.
Polarity (is signalled)
Over Range (is signalled)
C3._.2
Status Output Y
Only appears if output A to D is set under “Mode” (see above), and this output is a “Status
Output”.
Same Signal (like other connected status output, signal can be inverted, see below)
C3._.2
Limit Switch Y and
Control Input Y
Only appears if output A to D / input A or B is set under “Mode” (see above), and this
output / input is a “Limit Switch / Control Input”.
Status Off (is always selected here if Status Output X is connected with a Limit Switch /
Control Input Y).
C3._.2
Output Y
Only appears if output A to D is set under “Mode” (see above) and this output is switched
off.
C3._.3
Invert Signal
Select:
Off (activated output: switch closed) /
On (activated output: switch open)
C3._.4
Information
Serial no. of the I/O board, software version no. and production date of the circuit board
C3._.5
Simulation
Sequence see B1._ Status Output X