81
WWW.LCMETER.COM
LCI40
Series IOM
6 oPeration
legend
Fixed status signal
Variable status signal
Error Type Event Group
Single Event
Description
Actions to
Eliminate the
Event
FF
F Sensor
Sensor Containment Dam.
High pressure detected in housing. Faulty
measuring tube.
Exchange
measuring sensor.
Sensor Error
The measuring sensor signals are out of
range.
Flow measurements are not possible.
Check connection
between measuring
sensor and signal
converter (remote
version) or replace
measuring sensor.
FF
F Electronics
System Error
Electronics error in internal bus
communication or due to a hardware
error.
Perform cold
start. If message
reappears, contact
manufacturer.
System Error A
System Error C
HW Combination Error
BM Failure
DM Failure
Process Input Failure
IO 1 Failure
IO 2 Failure
Tot 1 Failure
Tot 2 Failure
Tot 3 Failure
IO A Failure
IO B Failure
IO C Failure
FF
F Configuration
BM Configuration
Error detected when starting device.
Possible causes: inadmissible parameter
settings or fault with electronics
component.
Check settings
of appropriate
function or load
factory settings.
If the error
persists, contact
manufacturer.
DM Configuration
Process Input Config.
Settings for process input invalid.
Check settings
for process input
or load factory
settings.
Density Calib.
Density calibration parameters invalid.
Perform density
calibration.
Check product and
function mode.
6.6 Status Messages and diagnostic information