9. Basic functions
9-4
SV-iC5
Frequency setting via Potentiometer on the Current Analog input (0-20mA)
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
Command]
-
-
-
Hz
Drive
group
Frq
[Frequency Mode]
5
0/8 0
Select Frq – [Frequency Mode] to 5 {Potentiometer on the keypad and Current Analog input (0-20mA)}.
Override function is provided via Main speed and Auxiliary speed adjustment.
Related code: I 1 - I 5, I 11- I 15
When main speed is set via potentiometer and Auxiliary speed via 0-20mA analog input, the override
function is set as below.
Group Code
Parameter
Name
Set
value
Units
I 2
[V0 input minimum voltage]
0
V
I 3
[Frequency corresponding to I 2]
0
Hz
I 4
[V0 input max voltage]
10
V
I 5
[Frequency corresponding to I 4]
60.0
Hz
I 12
[I input minimum current]
4
mA
I 13
[Frequency corresponding to I 12]
0
Hz
I 14
[I input max current]
20
mA
I/O group
I 15
[Frequency corresponding to I 14]
5.0
Hz
After the above setting is made, if 5V is set via potentiometer and 10mA is applied via I terminal, 32.5Hz is output
Frequency setting via 0-10V + 0-20mA input
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
Command]
-
-
-
Hz
Drive
group
Frq
[Frequency Mode]
6
0/8 0
Set
Frq
– [Frequency Mode] to 6 {V1 + I terminal input}.
Related code : I 6 - I 10, I 11 - I 15
Refer to the Frequency setting via Potentiometer on the Current Analog input (0-20mA) for the
setting.
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......