7. Function list
7-13
SV-iC5
Function group 2
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
H51
[P gain for PID
controller]
0/999.9
[%]
300.0 O
10-8
H52
[Integral time
for PID
controller
(I gain)]
0.1/32.0
[sec]
1.0 O
10-8
H53
Differential
time for PID
controller
(D gain)
0.0 /30.0
[sec]
This parameter sets the gains for the PID
controller.
0.0 O
10-8
H54
F gain for PID
controller
0/999.9
[%]
This is the Feed forward gain for the PID
controller.
0.0 O
10-8
H55
[PID output
frequency
limit]
0/400
[Hz]
This parameter limits the amount of the
output frequency thru the PID control.
The value is settable within the range of
F21 – [Max frequency] and H23 – [Start
frequency].
60.0 O
10-8
0
The Accel/Decel time is the time that
takes to reach the F21 – [Max
frequency] from 0 Hz.
H70 [Frequency
Reference for
Accel/Decel]
0/1
1
The Accel/Decel time is the time that
takes to reach a target frequency from
the run frequency.
0 X
9-10
0
Settable unit: 0.01 second.
1
Settable unit: 0.1 second.
H71 [Accel/Decel
time scale]
0/2
2
Settable unit: 1 second.
1 O
9-11
This parameter selects the parameter to be
displayed on the keypad when the input
power is first applied.
0 Frequency
command
1 Accel
time
2 Decel
time
3 Drive
mode
H72 [Power
on
display]
0/13
4 Frequency
mode
0 O
11-2
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......