9. Basic functions
9-8
SV-iC5
Run command setting 2 at FX and RX terminals
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Drive
group
drv
[Drive mode]
(Run/Stop mode)
2
0/3 1
I20
[Multi-function input terminal
P1 define]
0 0/24
0
I/O group
I21
[Multi-function input terminal
P2 define]
1 0/24
1
Set the
drv
to 2.
Set I20 and I21 to 0 and 1 to use P1 and P2 as FX and RX terminals.
FX: Run command setting. Motor runs in forward direction when RX terminal (P2) is OFF.
RX: Direction of motor rotation select. Motor runs in reverse direction when RX terminal (P2) is ON.
FX/RX Run Disable
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Drive
group
drC
[Direction of motor rotation
select]
- F/r
F
Function
group 1
F 1
[Forward/Reverse run
disable]
-
0/2 0
Select the direction of motor rotation.
0 : Forward and Reverse run enable
1 : Forward run disable
2 : Reverse run disable
FX
RX
Frequency