7. Function list
7-11
SV-iC5
Function group 2
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
H26 [Number
of
Auto Restart
try]
0/10
This parameter sets the number of
restart tries after a fault occurs.
Auto Restart is deactivated if the fault
outnumbers the restart tries.
This function is active when [drv] is set
to 1 or 2 {Run/Stop via control terminal}.
Deactivated during active protection
function (OHT, LVT, EXT, HWT etc.)
0 O
H27 [Auto
Restart
time]
0/60 [sec]
This parameter sets the time between
restart tries.
1.0 O
10-
15
0.2 0.2
kW
0.4 0.4
kW
0.75 0.75
kW
1.5 1.5
kW
H30 [Motor
type
select]
0.2/2.2
2.2 2.2
kW
-
1)
Automatically
set
X
H31 [Number
of
motor poles]
2/12
This setting is displayed via rPM in
drive group.
- X
H32 [Rated
slip
frequency]
0/10
[Hz]
×
−
=
120
P
rpm
f
f
r
s
Where,
s
f
= Rated slip frequency
r
f
= Rated frequency
rpm
= Motor nameplate RPM
P
= Number of Motor poles
-
2)
Automatically
set
X
H33 [Motor
rated
current]
1.0/20
[A]
Enter motor rated current on the
nameplate.
-
X
10-6
H34 [No
Load
Motor
Current]
0.1/12
[A]
Enter the current value detected when
the motor is rotating in rated rpm after the
load connected to the motor shaft is
removed.
Enter the 50% of the rated current
value when it is difficult to measure H34 -
[No Load Motor Current].
-
X
H36 [Motor
efficiency]
50/100
[%]
Enter the motor efficiency (see motor
nameplate).
-
X
10-6
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......