9. Basic functions
9-11
SV-iC5
More precise time unit can be set corresponding to load characteristics as shown below.
Code
Parameter Name
Setting range
Set
value
Description
0.01~600.00
0
Unit: 0.01 sec.
0.1~6000.0
1
Unit: 0.1 sec.
H71
[Accel/Decel Time setting
unit]
1~60000
2
Unit: 1 sec.
Accel/Decel time based on Run frequency
Group
LED display
Parameter name
Set
value
Min/Max
range
Factory
defaults
Unit
ACC [Accel
time]
-
0/6000
5.0 sec
Drive
group
dEC [Decel
time]
-
0/6000
10.0 sec
Function
group 2
H70
[Frequency reference for
Accel/Decel]
1
0/1 0
Accel/Decel time is set at the
ACC/dEC
.
If you set H70 to 1 {Delta frequency}, Accel/Decel time is the time that takes to reach a target freq from run
freq (Currently operating freq.).
When H70 and Accel time are set to 1 {Delta frequency} and 5 sec, respectively,
(A zone: run freq 10 Hz applied first, B zone: Operating via 10 Hz, different run freq is not issued
C: 30Hz Run freq (in this case, Target freq) issued while 10 Hz run freq is applied. But the preset accel time
5 sec is maintained. )
Run
command
Freq.
command
5
7
12
Time
[sec]
5 sec
5 sec
10Hz
30Hz
A
B
C
(Run freq.)
(Target freq.)
(Delta freq.)
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......