10. Advanced functions
10-2
SV-iC5
Starting DC brake
Group
LED Display
Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
F12
[DC Brake start voltage]
-
0/200 50
%
Function
group 1
F13
[DC Brake start time]
-
0/60 0
sec
F12 : It sets the level as a percent of H33 – [Motor rated current].
F13 : Motor accelerates after DC voltage is applied for the set time.
☞
Caution :
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and damage
to the motor.
Setting F12 or F13 to 0 will disable Starting DC brake.
t : After F13 -
[DC Brake start time]
, the frequency is increasing after DC voltage is applied until the
time t. In this case, DC Brake start time may be longer than the set value.
DC brake at a stop
Group
LED Display
Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
Function
group 1
F12
[DC Brake start voltage]
-
0/200 50
%
I/O group
I22
[Multi-function input
terminal P3 define]
11
0/24 2
F12 : Set as a percent of H33 – [Motor rated current].
Select a terminal to issue a command of DC brake during stop among P1 thru P5.
If P3 terminal is set for this function, set 22 to 11 {DC brake during stop}.
☞
Caution :
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and damage
to the motor.
Freq.
Voltage
Run
command
F13
t
F12
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......