12. Protective functions
12-2
SV-iC5
12.2 Overload Warning and trip
Overload warning
Group
LED Display
Parameter Name
Set
value
Min/Max
setting
Factory
default
Unit
F54
[Overload warning level]
-
30/150
150 %
Function
group 1
F55
[Overload warning time]
-
0/30
10 Sec
I54
[Multi-function output
terminal select]
5
12
I/O group
I55
[Multi-function relay select]
5
0/17
17
Select one output terminal for this function between MO and 30AC.
If selecting MO as output terminal, set I54 to 5 {Overload : OL}.
F54 : Set the value as a percent of motor rated current.
Current [%]
F51
F52
60
ETH trip time [sec]
Current
Multi-function
output
F54
t : Overload
warning time
t
t