11. Monitoring
11-5
SV-iC5
11.4 Analog Output
Group
LED Display
Parameter Name
Set
value
Min/Max
range
Factory
default
Unit
I50
[Analog output item
select]
-
0/3
0
I/O group
I51
[Analog output level
adjustment]
-
10/200
100 %
Output item and the level from the AM terminal are selectable and adjustable.
I50 : The selected item will be output to Analog output terminal (AM).
10V
0
Output frequency.
Max Frequency (F21)
1
Output current
150% of Inverter rated current
2
Output voltage
282 Vac
I50 Analog output
item select
3
Inverter DC link
voltage
400 Vdc
I51 : If you want to use Analog output value as a gauge input , the value can be adjustable
corresponding to various gauge specifications.
AM
CM
0 ~ 10Vdc
Fault type
Operating status
when a fault
occurs
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......