7. Function list
7-10
SV-iC5
Function group 2
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
This parameter is active to prevent any
possible fault when the inverter outputs its
voltage to the running motor.
1. H20-
[Power
On start]
2.Restart
after
instant
power
failure
3.Operation
after fault
occurred
4.Normal
acceler-
ation
Bit 3
Bit 2
Bit 1
Bit 0
0 - -
-
-
1 - -
-
3
2 - -
3
3 - -
3
3
4 -
3
- -
5 -
3
-
3
6 -
3
3
7 -
3
3
3
8
3
- - -
9
3
- -
3
10
3
-
3
-
11
3
-
3
3
12
3
3
- -
13
3
3
-
3
14
3
3
3
-
H22
2)
[Speed
Search Select]
0/15
15
3
3
3
3
0 O
10-
12
H23 [Current
level
during Speed
search]
80/200
[%]
This parameter limits the amount of current
during speed search.
The set value is the percentage of the H33-
[Motor rated current].
100 O
H24
[P gain during
Speed search]
0/9999
It is the Proportional gain used for Speed
Search PI controller.
100 O
H25
[I gain during
speed search]
0/9999
It is the Integral gain used for Speed search
PI controller.
1000 O
10-
12
2)
#4.Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter starts Speed search #4.
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......