7. Function list
7-16
SV-iC5
I/O group
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
I 0
[Jump code]
0/63
This parameter sets the code number to jump
1
O
5-5
I 1
[Filter time
constant for
V0 input]
0/9999
This is used to adjust the analog voltage input
signal via keypad potentiometer.
10 O
I 2
[V0 input Min
voltage]
0/10
[V]
Set the minimum voltage of the V0 input.
0
O
I 3
[Frequency
corresponding
to I 2 ]
0/400
[Hz]
Set the inverter output minimum frequency at
minimum voltage of the V0 input.
0.0 O
I 4
[V0 input Max
voltage]
0/10
[V]
Set the maximum voltage of the V0 input.
10
O
I 5
[Frequency
corresponding
to I 4]
0/400
[Hz]
Set the inverter output maximum frequency at
maximum voltage of the V0 input.
60.0 O
9-2
I 6
[Filter time
constant for
V1 input]
0/9999
Set the input section’s internal filter constant for
V1 input.
10 O
I 7
[V1 input Min
voltage]
0/10
[V]
Set the minimum voltage of the V1 input.
0
O
I 8
[Frequency
corresponding
to I 7]
0/400
[Hz]
Set the inverter output minimum frequency at
minimum voltage of the V1 input.
0.0 O
I 9
[V1 input max
voltage]
0/10
[V]
Set the maximum voltage of the V1 input.
10
O
I10 [Frequency
corresponding
to I 9]
0/400
[Hz]
Set the inverter output maximum frequency at
maximum voltage of the V1 input.
60.0 O
9-3
I11 [Filter
time
constant for I
input]
0/9999
Set the input section’s internal filter constant for
I input.
10 O
I12 [I
input
minimum
current]
0/20
[mA]
Set the Minimum Current of I input.
4
O
9-4
Содержание SV-iC5 Series
Страница 8: ...Table of Contents viii SV iC5 ...
Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...
Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Страница 64: ......
Страница 68: ......
Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Страница 136: ......