Thank you for purchasing LG Variable Frequency Drives! 

 

SAFETY INSTRUCTIONS 

 

 

 

Always follow safety instructions to prevent accidents and potential hazards from occurring.   

 

 

In this manual, safety messages are classified as follows: 

 

   

WARNING

   

 

CAUTION 

 

 

 

Throughout this manual we use the following two illustrations to make you aware of safety considerations: 

 

  Identifies potential hazards under certain conditions.   
  Read the message and follow the instructions carefully.

 

 

                

Identifies shock hazards under certain conditions.   

  Particular attention should be directed because dangerous voltage may be present. 

 

 

 

 

Keep operating instructions handy for quick reference. 

 

 

Read this manual carefully to maximize the performance of SV-iC5 series inverter and ensure its safe use. 

 

 

 

WARNING 

 
 

 

Do not remove the cover while power is applied or the unit is in operation.   

Otherwise, electric shock could occur.

 

 

 

Do not run the inverter with the front cover removed.   

Otherwise, you may get an electric shock due to high voltage terminals or charged capacitor 
exposure.

 

 

 

Do not remove the cover except for periodic inspections or wiring, even if 

the input power is not applied.   

 

Otherwise, you may access the charged circuits and get an electric shock.

 

 

 

Wiring and periodic inspections should be performed at least 10 minutes 

after disconnecting the input power and after checking the DC link voltage 
is discharged with a meter (below DC 30V).   

Otherwise, you may get an electric shock.   

 

 

Operate the switches with dry hands. 

Otherwise, you may get an electric shock.

 

 

 

Do not use the cable when its insulating tube is damaged. 

 

 

Otherwise, you may get an electric shock.

 

 

 

Do not subject the cables to scratches, excessive stress, heavy loads or 

Improper operation may result in slight to medium personal injury 
or property damage.

 

Improper operation may result in serious personal injury or death.

 

Содержание SV-iC5 Series

Страница 1: ...s applied or the unit is in operation Otherwise electric shock could occur Do not run the inverter with the front cover removed Otherwise you may get an electric shock due to high voltage terminals or charged capacitor exposure Do not remove the cover except for periodic inspections or wiring even if the input power is not applied Otherwise you may access the charged circuits and get an electric s...

Страница 2: ...S 1 Handling and installation Handle according to the weight of the product Do not stack the inverter boxes higher than the number recommended Install according to instructions specified in this manual Do not open the cover during delivery Do not place heavy items on the inverter Check the inverter mounting orientation is correct Do not drop the inverter or subject it to impact Use the Type 3 grou...

Страница 3: ...Motor might not be protected by electronic thermal function of inverter Do not use a magnetic contactor on the inverter input for frequent starting stopping of the inverter Use a noise filter to reduce the effect of electromagnetic interference Otherwise nearby electronic equipment may be affected In case of input voltage unbalance install AC reactor Power Factor capacitors and generators may beco...

Страница 4: ... the inverter 5 Programming keypad Illustrates keypad features and display 6 Basic operation Provides instructions for quick start of the inverter 7 Function list Outlines the parameter information of the SV iC5 such as description type units factory defaults minimum maximum setting 8 Control block diagram Shows control flow to help users easily understand operation mode 9 Basic functions Provides...

Страница 5: ...lection and connector for communication option 3 5 4 Basic configuration 4 1 4 1 Connection of peripheral devices to the inverter 4 1 4 2 Recommended MCCB Earth leakage circuit breaker ELB and Magnetic contactor specification 4 2 4 3 Recommendable AC DC Reactor 4 2 5 Programming Keypad 5 1 5 1 Keypad features 5 1 5 2 Alpha numeric view on the LED keypad 5 2 5 3 Moving to other groups 5 3 5 4 How t...

Страница 6: ... DC brake 10 1 10 2 Jog operation 10 3 10 3 Up Down operation 10 4 10 4 3 Wire Operation 10 4 10 5 Dwell operation 10 5 10 6 Slip compensation 10 6 10 7 PID Control 10 8 10 8 Auto tuning 10 10 10 9 Sensorless vector control 10 11 10 10 Energy saving operation 10 12 10 11 Speed Search 10 12 10 12 Auto restart try 10 15 10 13 Second motor operation 10 16 10 14 Parameter initialize Lock 10 17 11 Moni...

Страница 7: ...ternal trip signal 12 5 12 6 Inverter Overload 12 6 12 7 Frequency command loss 12 7 13 Troubleshooting Maintenance 13 1 13 1 Protective functions 13 1 13 2 Fault Remedy 13 3 13 3 Precautions for maintenance and inspection 13 5 13 4 Check points 13 5 13 5 Part replacements 13 5 14 Specifications 14 1 14 1 Technical data 14 1 14 2 Temperature Derating Information 14 3 DECLARATION OF CONFORMITY i ...

Страница 8: ...Table of Contents viii SV iC5 ...

Страница 9: ...ase N A Accessories If you have found any discrepancy damage etc contact your sales representative Preparations of instruments and parts required for operation Instruments and parts to be prepared depend on how the inverter is operated Prepare equipment and parts as necessary Installation To operate the inverter with high performance for a long time install the inverter in a proper place in the co...

Страница 10: ...ove it when wiring input power and motor Status LED Display Window Inverter Nameplate 4 Way button for parameter setting Up Down Left Right key Analog Input Output Terminal NPN PNP Select Switch Keypad Potentiometer STOP RST Button RUN Button Inverter Ground Terminal Caution Remove the bottom cover to access the terminal Body slot When front cover is pulled back till this line and lifted up it can...

Страница 11: ... way button will appear Use this button for parameter setting and changing the value Removal for wiring The method is the same as shown in 1 Hold both sides of the cover and lift upward to completely remove from the main body 1 Push down the cover until cover top matches the side slot 1 2 1 2 1 Press here gently 2 Push it down 4 Way Button 3 Lift it up to remove 2 Hold both sides of this part Para...

Страница 12: ...ess control terminals after finishing power terminal wiring reinstall the bottom cover and then start wiring control terminals Note Use the recommended size of the cable as indicated in this manual ONLY Using larger size cable may lead to mis wiring or damage the insulation Note Input Power Terminals name is labeled here Note Control Terminals name is labeled here ...

Страница 13: ...sed in Ambient 40 C UL 508C Ambient Temp Checking Location The inverter will be very hot during operation Install it on a non combustible surface Mount the inverter on a flat vertical and level surface Inverter orientation must be vertical top up for proper heat dissipation Also leave sufficient clearances around the inverter Protect from moisture and direct sunlight Do not install the inverter in...

Страница 14: ...ent temperature of the inverters below the permissible value If they are installed in improper positions the ambient temperature of the inverters will rise and ventilation effect will be reduced Install the inverter using screws or bolts to insure the inverter is firmly fastened For installing multiple inverters in panel Note Take caution on proper heat ventillation when installing inverters and f...

Страница 15: ...2 Installation 2 3 SV iC5 2 2 Dimensions 0 4 0 75 kW 1 2 1 HP Dimension 004iC5 1 004iC5 1F 008iC5 1 008iC5 1F W 79 79 79 79 H 143 143 143 143 D 143 143 143 143 Weight Kg 0 87 0 95 0 89 0 97 W D H ...

Страница 16: ...2 Installation 2 4 SV iC5 1 5 2 2 kW 2 3HP Dimension 015iC5 1 015iC5 1F 022iC5 1 022iC5 1F W 156 156 156 156 H 143 143 143 143 D 143 143 143 143 Weight Kg 1 79 1 94 1 85 2 W D H ...

Страница 17: ...inal Common Terminal for P1 P5 AM P24 24V power for P1 P5 Initial setting FX Forward run RX Reverse run BX Emergency stop JOG Jog operation RST Fault reset 12V power supply for potentiometer 0 10V Analog Input terminal 0 20mA Analog Input terminal AM Multi function Analog output terminal 0 10V CM Common terminal for AM terminal EXTG Multi function open collector output terminal Ground T M for MO A...

Страница 18: ...working on it If tester is available check the voltage between P1 and N terminals Wiring should be performed after verifying that input voltage in inverter DC circuitry is all exhausted Applying input power supply to the output terminals U V and W causes internal inverter damage Use ring terminals with insulated caps when wiring the input power and motor wiring Do not leave wire fragments inside t...

Страница 19: ...the screw in the case or chassis etc for grounding Note Remove front and bottom cover before starting grounding Caution Follow the specifications below when grounding the inverter Model 004iC5 008iC5 1 1F 015iC5 022iC5 1 1F Wire size 2mm2 2mm2 Lug 2mm2 3φ 2mm2 3φ Ground impedance Below 100 ohm Below 100 ohm Dedicated Ground Terminal Dedicated Ground Terminal ...

Страница 20: ... 0 3 mm2 0 4 AM Multi function Analog output 22 AWG 0 3 mm2 0 4 MO Multi function open collector output T M 20 AWG 0 5 mm2 0 4 EXTG Ground T M for MO 20 AWG 0 5 mm2 0 4 P24 24V Power Supply for P1 P5 20 AWG 0 5 mm2 0 4 30A 20 AWG 0 5 mm2 0 4 30B Multi function relay A B contact output 20 AWG 0 5 mm2 0 4 30C 30A B Common 20 AWG 0 5 mm2 0 4 Note Tie the control wires more than 15cm away from the con...

Страница 21: ...ble for SV iC5 Refer to MODBUS RTU option card manual for more details CM FX 24X 24I CM CM Resistor Resistor Resistor CPU S4 CM FX 24X 24I CM CM Resistor Resistor Resistor CPU S4 2 When using 24V external power supply PNP 1 When using P24 NPN 2 Communication Option Card Connector Install Communication option card here ...

Страница 22: ...3 Wiring 3 6 SV iC5 Notes ...

Страница 23: ...breaker ELB Select circuit breakers with care A large inrush current may flow in the inverter at power on Magnetic Contactor Install it if necessary When installed do not use it for the purpose of starting or stopping Otherwise it could lead to reduction in product life AC DC Reactors The reactors must be used when the power factor is to be improved or the inverter is installed near a large power ...

Страница 24: ...te 004iC5 1 1F ABS33b EBS333 GMC 12 008iC5 1 1F ABS33b EBS333 GMC 18 015iC5 1 1F ABS33b EBS333 GMC 25 022iC5 1 1F ABS33b EBS333 GMC 32 4 3 Recommendable AC DC Reactor Model AC input fuse AC reactor DC reactor 004iC5 1 1F 10A 2 13mH 5 7A 7 00mH 5 4A 008iC5 1 1F 20A 1 20mH 10A 4 05mH 9 2A 015iC5 1 1F 30A 0 88mH 14A 2 92mH 13 A 022iC5 1 1F 40A 0 56mH 20A 1 98mH 19 A ...

Страница 25: ...w and Prog Ent keys S UP Used to scroll through codes or increase parameter value T Down Used to scroll through codes or decrease parameter value W Left Used to jump to other parameter groups or move a cursor to the left to change the parameter value X Right Used to jump to other parameter groups or move cursor to the right to change the parameter value z Prog Ent key Used to set the parameter val...

Страница 26: ...5 Programming keypad 5 2 SV iC5 5 2 Alpha numeric view on the LED keypad 0 A K U 1 B L V 2 C M W 3 D N X 4 E O Y 5 F P Z 6 G Q 7 H R 8 I S 9 J T ...

Страница 27: ...on I O Input Output group Parameters necessary to make up a sequence using Multi function input output terminal Moving to other parameter groups is only available in the first code of each group as the figure shown below Moving to other groups using the Right X key Moving to other groups using the Left W key Function group 1 Function group 2 I O group Drive group Function group 1 Function group 2 ...

Страница 28: ... displayed Press the right arrow X key once again to return to Drive group 5 Return to the 1st code in Drive group 0 0 If the left arrow key W is used the above will be executed in the reverse order How to move to other groups from any codes other than the 1st code When you would like to move from the F 15 to function group 2 1 In F 15 press the Left W or Right arrow X key Pressing the key goes to...

Страница 29: ...eturn to the first code of Drive group Drive group Use Down T key for the opposite order Code change in Function group 1 When moving from the F 0 to the F 15 directly 1 Press the Prog Ent z key in F 0 2 1 the code number of F1 is displayed Use the Up S key to set to 5 3 05 is displayed by pressing the Left W key once to move the cursor to the left The numeral having a cursor is displayed brighter ...

Страница 30: ...2 and I O group Note Some codes will be skipped in the middle of increment S decrement T for code change That is because it is programmed that some codes are intentionally left blank for future use or the codes user does not use are invisible For example when F23 High low frequency limit select is set to O No F24 High frequency limit and F23 Low frequency limit are not displayed during code change...

Страница 31: ... digit 5 in 5 0 is active Then press the Up S key once 5 The value is increased to 6 0 Press the Left W key to move the cursor to the left 6 0 60 is displayed The first 0 in 0 60 is active Press the Up S key once 7 16 0 is set Press the Prog Ent z key once 16 0 is blinking Press the Prog Ent z key once again to return to the parameter name 8 ACC is displayed Accel time is changed from 5 0 to 16 0 ...

Страница 32: ...Press the Left W key once 6 Press the Left W key once 7 00 0 is displayed with the first 0 active but the actual value 0 05 remains unchanged Press the Up S key to set to 3 8 Press the Prog Ent z key once 30 0 is blinking Press the Prog Ent z key once 9 Run frequency is set to 30 0 when the blinking stops Three digit LED display is provided in SV iC5 Series However digit expansion is available usi...

Страница 33: ...e the value to 2 by pressing the Up S key 5 27 is displayed Press the Prog Ent z key once 6 The parameter number F27 is displayed Press the Prog Ent z key once to check the set value 7 The set value is 0 Increase the value to 1 by pressing the Up S key 8 Press the Prog Ent z key once 9 F27 is displayed after 5 stops blinking Changing parameter value has been complete Press the either Left W or Rig...

Страница 34: ...yed 2 Monitoring output current is provided in this parameter Press the Prog Ent z key once to check the current 3 Present output current is 5 0 A Press the Prog Ent z key once to return to the parameter name 4 Return to the output current monitoring code Other parameters in Drive group such as dCL Inverter DC link current or vOL Inverter output voltage can be monitored via the same method ...

Страница 35: ...de of Function group 1 The preset frequency is 57 6Hz Continue pressing the Up S Down T key until rPM is displayed 2 Motor rpm can be monitored in this code Press the Prog Ent z key once 3 Last three digits 730 in 1730 rpm is shown on the LED Press the Left W key once 4 First three digits 173 in 1730 rpm are shown on the LED Press the Prog Ent z key once 5 Return to the rPM code ...

Страница 36: ... at the time of fault 30 0 is displayed Press the Up S key once 3 The output current at the time of fault is displayed Press the Up S key once 4 Operating status is displayed A fault occurred during acceleration Press the STOP RST key once 5 A fault condition is cleared and nOn is displayed When more than one fault occur at the same time Drive group Over current Over voltage Motor overheating Maxi...

Страница 37: ...ove the cursor to the left 4 03 is displayed 0 in 03 is active Increase the value to 9 by pressing the Up S key 5 93 is set Press the Prog Ent z key once 6 The parameter number is displayed Press the Prog Ent z key once 7 Present setting is 0 Press the Up S key once to set to 1 to activate parameter initialize 8 Press the Prog Ent z key once 9 Return to the parameter number after blinking Paramete...

Страница 38: ...5 Programming keypad 5 14 SV iC5 Notes ...

Страница 39: ...wn left Press the Left W key twice 4 00 0 is displayed and the first 0 is lit Press the Up S key 5 10 0 is set Press the Prog Ent z key once 10 0 is blinking Press the Prog Ent z key once 6 Run frequency is set to 10 0 Hz when the blinking stops Turn on the switch between P1 FX and CM terminals 7 FWD Forward run lamp begins to blink and accelerating frequency is displayed on the LED When target ru...

Страница 40: ...splayed after 2 stops blinking Turn the potentiometer to set to 10 0 Hz in either Max or Min direction 7 Turn on the switch between P1 FX and CM See Wiring below FWD lamp begins to blink and the accelerating frequency is displayed on the LED When run frequency 10Hz is reached the value is displayed as shown left Turn off the switch between P1 FX and CM terminals 8 FWD lamp begins to blink and the ...

Страница 41: ...heck the present frequency setting method 0 is run via keypad Press the Up S key twice 9 After checking 2 frequency setting via potentiometer press the Prog Ent z key 10 Frq is displayed after 2 is blinking Frequency setting is set via the potentiometer on the keypad Turn the potentiometer to set to 10 0 Hz in either Max or Min direction 11 Press the Run key on the keypad FWD lamp begins to blink ...

Страница 42: ...6 Basic operation 6 4 SV iC5 Notes ...

Страница 43: ... Stop via control terminal FX Run Stop enable RX Reverse rotation select 9 7 Drv Drive mode Run Stop mode 0 3 3 Operation via Communication Option 1 X 0 Setting via Keypad 1 9 1 1 Digital Setting via Keypad 2 9 1 2 Setting via potentiometer on the keypad V0 9 2 3 Setting via V1 terminal 9 3 4 Setting via I terminal 9 3 5 Setting via potentiometer on the keypad I terminal 9 4 6 Setting via V1 I ter...

Страница 44: ...age This parameter displays DC link voltage inside the inverter 11 1 This parameter displays the item selected at H73 Monitoring item select vOL Output voltage POr Output power vOL User display select tOr Torque vOL 11 2 nOn Fault Display This parameter displays the types of faults frequency and operating status at the time of the fault 11 2 This parameter sets the direction of motor rotation when...

Страница 45: ...s reached the inverter holds the output for the setting time before starting DC brake 0 1 X 10 1 F10 DC Brake voltage 0 200 This parameter sets the amount of DC voltage applied to a motor It is set in percent of H33 Motor rated current 50 X 10 1 F11 DC Brake time 0 60 sec This parameter sets the time taken to apply DC current to a motor while motor is at a stop 1 0 X 10 1 F12 DC Brake start voltag...

Страница 46: ...ameplate In case of using a 50Hz motor set this to 50Hz 60 0 X 9 15 F23 Start frequency 0 10 Hz The inverter starts to output its voltage at this frequency It is the frequency low limit 0 5 X 9 19 F24 Frequency high low limit select 0 1 This parameter sets high and low limit of run frequency 0 X F25 2 Frequency high limit 0 400 Hz This parameter sets high limit of the run frequency It cannot be se...

Страница 47: ...ser V F frequency 4 0 400 Hz 60 0 X F38 User V F voltage 4 0 100 This parameter is active when F30 V F pattern is set to 2 User V F It cannot be set above F21 Max frequency The value of voltage is set in percent of H70 Motor rated voltage The values of the lower numbered parameters cannot be set above those of higher numbered 100 X 9 16 F39 Output voltage adjustment 40 110 This parameter adjusts t...

Страница 48: ... using a separate motor to power a cooling fan 0 0 12 1 F54 Overload warning level 30 150 This parameter sets the amount of current to issue an alarm signal at a relay or multi function output terminal see I54 I55 The set value is the percentage of H33 Motor rated current 150 0 F55 Overload warning time 0 30 sec This parameter issues an alarm signal when the current greater than F54 Overload warni...

Страница 49: ... run and stops decelerating during deceleration During Deceleration During constant speed During Acceleration Bit 2 Bit 1 Bit 0 0 1 3 2 3 3 3 3 4 3 5 3 3 6 3 3 F59 Stall prevention select 0 7 7 3 3 3 0 X 12 3 F60 Stall prevention level 30 150 This parameter sets the amount of current to activate stall prevention function during Accel constant or Decel run The set value is the percentage of the H33...

Страница 50: ...F23 400 Hz When run frequency is issued motor starts to accelerate after dwell frequency is applied to the motor during H8 Dwell time Dwell frequency can be set within the range of F21 Max frequency and F23 Start frequency 5 0 X H 8 Dwell time 0 10 sec This parameter sets the time for dwell operation 0 0 X 10 5 H10 Skip frequency select 0 1 This parameter sets the frequency range to skip to preven...

Страница 51: ...igher linear zone gets smaller 40 X 9 13 H19 Output phase loss protection select 0 1 Inverter turns off the output when the phase of the inverter output U V W is not properly connected 0 O 12 5 H20 Power On Start select 0 1 This parameter is activated when drv is set to 1 or 2 Run Stop via Control terminal Motor starts acceleration after AC power is applied while FX or RX terminal is ON 0 O H21 Re...

Страница 52: ...7 3 3 3 8 3 9 3 3 10 3 3 11 3 3 3 12 3 3 13 3 3 3 14 3 3 3 H22 2 Speed Search Select 0 15 15 3 3 3 3 0 O 10 12 H23 Current level during Speed search 80 200 This parameter limits the amount of current during speed search The set value is the percentage of the H33 Motor rated current 100 O H24 P gain during Speed search 0 9999 It is the Proportional gain used for Speed Search PI controller 100 O H25...

Страница 53: ... 0 4 kW 0 75 0 75 kW 1 5 1 5 kW H30 Motor type select 0 2 2 2 2 2 2 2 kW 1 Automatically set X H31 Number of motor poles 2 12 This setting is displayed via rPM in drive group X H32 Rated slip frequency 0 10 Hz 120 P rpm f f r s Where s f Rated slip frequency r f Rated frequency rpm Motor nameplate RPM P Number of Motor poles 2 Automatically set X H33 Motor rated current 1 0 20 A Enter motor rated ...

Страница 54: ...leakage current will become greater 3 O 10 16 0 Volts frequency Control 9 15 1 Slip compensation control 10 6 2 PID Feedback control 10 8 H40 Control mode select 0 3 3 Sensorless vector control 0 X 10 11 H41 Auto tuning 0 1 If this parameter is set to 1 it automatically measures parameters of the H42 and H43 0 X H42 Stator resistance Rs 0 5 0 Ω This is the value of the motor stator resistance X H4...

Страница 55: ...ameter limits the amount of the output frequency thru the PID control The value is settable within the range of F21 Max frequency and H23 Start frequency 60 0 O 10 8 0 The Accel Decel time is the time that takes to reach the F21 Max frequency from 0 Hz H70 Frequency Reference for Accel Decel 0 1 1 The Accel Decel time is the time that takes to reach a target frequency from the run frequency 0 X 9 ...

Страница 56: ...ut power kW H73 Monitoring item select 0 2 2 Torque kgf m 0 O 11 2 H74 Gain for Motor rpm display 1 1000 This parameter is used to change the motor speed display to rotating speed r min or mechanical speed m mi 100 O 11 1 H79 Software version 0 10 0 This parameter displays the inverter software version X X X H81 2 nd motor Accel time 5 0 O H82 2 nd motor Decel time 0 6000 sec 10 0 O H83 2 nd motor...

Страница 57: ... X 10 16 This parameter is used to initialize parameters back to the factory default values 0 1 All parameter groups are initialized to factory default value 2 Only Drive group is initialized 3 Only Function group 1 is initialized 4 Only Function group 2 is initialized H93 Parameter initialize 0 5 5 Only I O group is initialized 0 X 10 17 H94 Password register 0 FFF Password for H95 Parameter lock...

Страница 58: ... corresponding to I 4 0 400 Hz Set the inverter output maximum frequency at maximum voltage of the V0 input 60 0 O 9 2 I 6 Filter time constant for V1 input 0 9999 Set the input section s internal filter constant for V1 input 10 O I 7 V1 input Min voltage 0 10 V Set the minimum voltage of the V1 input 0 O I 8 Frequency corresponding to I 7 0 400 Hz Set the inverter output minimum frequency at mini...

Страница 59: ...put Signal loss 0 2 2 Below the value set in I 2 7 12 entered 0 O 12 7 0 Forward run command FX I20 Multi function input terminal P1 define 1 Reverse run command RX 0 O 9 7 2 Emergency Stop Trip EST I21 Multi function input terminal P2 define 3 Reset when a fault occurs RST 1 O 4 Jog operation command JOG 10 3 I22 Multi function input terminal P3 define 5 Multi Step frequency Low 2 O 6 Multi Step ...

Страница 60: ...4 Accel Decel Disable BIT4 BIT3 BIT2 BIT1 BIT0 I25 Input terminal status display P5 P4 P3 P2 P1 11 3 BIT1 BIT0 I26 Output terminal status display 30AC MO 11 3 I27 Filtering time constant for Multi function Input terminal 2 50 If the value is set higher the response of the Input terminal is getting slower 15 O I30 Multi Step frequency 4 30 0 O I31 Multi Step frequency 5 25 0 O I32 Multi Step freque...

Страница 61: ...0 Multi Accel time 4 6 0 I41 Multi Decel time 4 6 0 I42 Multi Accel time 5 7 0 I43 Multi Decel time 5 7 0 I44 Multi Accel time 6 8 0 I45 Multi Decel time 6 8 0 I46 Multi Accel time 7 9 0 I47 Multi Decel time 7 9 0 9 12 10 V Output Output item 200V 400V 0 Output frequency Max frequency 1 Output current 150 2 Output voltage 282 V I50 Analog output item select 0 3 3 DC link voltage DC 400V 0 O I51 An...

Страница 62: ...i function output terminal select 1 FDT 2 12 11 6 2 FDT 3 11 8 3 FDT 4 11 8 4 FDT 5 11 9 5 Overload OL 6 Inverter Overload IOL 7 Motor stall STALL 8 Over voltage trip OV 9 Low voltage trip LV 10 Inverter heatsink overheat OH 11 Command loss 11 9 12 During run 13 During stop 14 During constant run 15 During speed searching 16 Wait time for run signal input I55 Multi function relay select 0 17 17 Fa...

Страница 63: ... bps 3 9600 bps I61 Baud rate 0 4 4 19200 bps 3 O It is used when frequency command is given via V1 and I terminal or communication option 0 Continuous operation 1 Free Run stop Coast to stop I62 Drive mode select after loss of frequency command 0 2 2 Decel to stop 0 O I63 Wait time after loss of frequency command 0 1 12 sec This is the time inverter determines whether there is the input frequency...

Страница 64: ......

Страница 65: ...8 Control block diagram 8 1 SV iC5 8 Control block diagram Frequency setting Drive mode Accel Decel V F control PWM Motor ...

Страница 66: ...O group I20 I24 FX RX run command setting via Multi function terminal I O group I20 I24 3 Wire operation F 1 FX RX Run Disable 5 6 7 0 1 17 Drive group drv Run command setting 0 1 2 LED 1 2 1 2 FX RX run enable 0 I O group I20 I24 Up Down operation I O group I20 I24 Jog operation Functi on group 1 F21 F23 Max Min frequency 15 16 Func group1 F20 Jog frequency 4 P1 P5 Frequency setting Run command F...

Страница 67: ...roup F25 Freq high low limit F26 0 1 7 Run command DC brake voltage time Dwell freq time V F pattern 0 1 2 Square User V F Freq Voltage Torque boost select Torque boost value 0 1 Automatic Manual Linear User V F Output voltage adjustment Base start freq PWM Operation Stop Frequency setting Func group1 F8 F11 Func group1 F4 Func group1 F2 F3 Func group1 H70 Func group1 F21 Drive group ACC DEC 1st 7...

Страница 68: ......

Страница 69: ... and press the Prog Ent z key to enter the value into memory The value is settable not greater than F21 Max frequency Digital Frequency setting via Keypad 2 Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit 0 0 Frequency Command 0 400 0 0 Hz Drive group Frq Frequency mode 1 0 8 0 Run frequency is settable in 0 0 Frequency Command Set Frq Frequency mode to 1 Frequency s...

Страница 70: ...et Frq Frequency Mode to 2 The set frequency can be monitored in 0 0 Frequency Command I 1 Filtering time constant for V0 input Effective for eliminating noise in the frequency setting circuit Increase the filter time constant if steady operation cannot be performed due to noise A larger setting results in slower response t gets longer I 2 I 5 Min Max input voltage and corresponding frequency sett...

Страница 71: ...om an external controller or a potentiometer between VR and CM terminals Wire the terminal as shown below and refer to page 9 2 for I 6 I10 Frequency Setting via Analog Current Input 0 20mA Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit 0 0 Frequency Command Hz Drive group Frq Frequency Mode 4 0 8 0 I11 Filtering time constant for I input 10 0 9999 10 I12 I input mi...

Страница 72: ...alue Units I 2 V0 input minimum voltage 0 V I 3 Frequency corresponding to I 2 0 Hz I 4 V0 input max voltage 10 V I 5 Frequency corresponding to I 4 60 0 Hz I 12 I input minimum current 4 mA I 13 Frequency corresponding to I 12 0 Hz I 14 I input max current 20 mA I O group I 15 Frequency corresponding to I 14 5 0 Hz After the above setting is made if 5V is set via potentiometer and 10mA is applied...

Страница 73: ...etting via potentiometer on the Keypad 0 20mA input for the setting Analog Hold Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Drive group Frq Frequency Mode 2 7 0 8 0 I20 Multi function input terminal P1 define 0 I O group I24 Multi function input Terminal P5 Define 23 0 24 4 This setting becomes activated when Frq Frequency Mode is set to 2 7 Set one of the Multi ...

Страница 74: ... 4 I30 Multi Step frequency 4 30 0 I31 Multi Step frequency 5 25 0 I32 Multi Step frequency 6 20 0 I O group I33 Multi Step frequency 7 0 400 15 0 Hz Select a terminal to give Multi step frequency command among P1 P5 terminals If terminals P3 P5 are selected for this setting set I22 I24 to 5 7 to give Multi step frequency command Multi step frequency 0 is settable using Frq Frequency mode and 0 0 ...

Страница 75: ...tion of motor rotation select when run command is issued via Run key on keypad F Forward drC Direction of motor rotation select R Reverse Run command setting 1 via FX and RX terminals Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Drive group drv Drive mode Run Stop mode 1 0 3 1 I20 Multi function input terminal P1 define 0 0 24 0 I O group I21 Multi function input ...

Страница 76: ... 1 to use P1 and P2 as FX and RX terminals FX Run command setting Motor runs in forward direction when RX terminal P2 is OFF RX Direction of motor rotation select Motor runs in reverse direction when RX terminal P2 is ON FX RX Run Disable Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Drive group drC Direction of motor rotation select F r F Function group 1 F 1 Forw...

Страница 77: ...on due to potential hazard as motor starts to run suddenly upon applying AC input power Restart after fault reset Group LED display Parametern name Set value Min Max range Factory defaults Unit Drive group Drv Drive mode Run Stop mode 1 2 0 3 1 Function group 2 H21 Restart after fault reset 1 0 1 0 Set H21 to 1 Motor starts acceleration if drv is set to 1 or 2 and the selected terminal is ON when ...

Страница 78: ...1 0 Function group 2 H71 Accel Decel Time setting unit 0 2 1 Set the desired Accel Decel time at ACC dEC in Drive group If H70 is set to 0 Max frequency Accel Decel time is the time that takes to reach the max freq from 0 Hz Desired Accel Decel time unit is settable at the H71 Accel Decel time is set based on F21 Max frequency For instance if F21 is set to 60Hz Accel Decel time 5 sec and run frequ...

Страница 79: ...e 0 6000 10 0 sec Function group 2 H70 Frequency reference for Accel Decel 1 0 1 0 Accel Decel time is set at the ACC dEC If you set H70 to 1 Delta frequency Accel Decel time is the time that takes to reach a target freq from run freq Currently operating freq When H70 and Accel time are set to 1 Delta frequency and 5 sec respectively A zone run freq 10 Hz applied first B zone Operating via 10 Hz d...

Страница 80: ... terminal P3 define 8 2 I23 Multi function input terminal P4 define 9 3 I24 Multi function input terminal P5 define 10 0 24 4 I34 Multi Accel time 1 3 0 I O group I47 Multi Decel time 7 0 6000 9 0 Sec Set I22 I23 I24 to 8 9 10 if you want to set Multi Accel Decel time via P3 P5 terminals Multi Accel Decel time 0 is settable at ACC and dEC Multi Accel Decel time 1 7 is settable at I34 I47 Multi Acc...

Страница 81: ...el Decel pattern is settable at F2 and F3 Linear This is a general pattern for constant torque applications S curve This curve allows the motor to accelerate and decelerate smoothly Appropriate applications Elevator door lifts Caution For S curve the actual Accel Decel time takes longer than the time set by user Run command Freq Accel time Decel time Freq H17 H17 H18 H18 Accel Decel Ref Freq Accel...

Страница 82: ...Min Max range Factory defaults Unit I20 Multi function input terminal P1 define 0 I O group I24 Multi function input terminal P5 define 24 0 24 4 Select one terminal of I20 24 to define Accel Decel disable For example if P5 is selected set I24 to 24 to activate this function ON Freq P5 Run command ON ON Freq H17 H17 H18 H18 Accel decel Ref Freq H70 Target Freq Note If set target freqis below Max f...

Страница 83: ...This is appropriate for constant torque applications F22 Base frequency Inverter outputs its rated voltage at this level Enter the motor nameplate frequency F23 Start frequency Inverter starts to output its voltage at this level Square V F operation Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Function group 1 F30 V F pattern 1 0 2 0 Set F30 to 1 Square This patte...

Страница 84: ... V F pattern it could result in torque shortage or motor overheating due to over energizing When User V F pattern is active F28 Torque Boost in forward direction and F29 Torque Boost in reverse direction are deactivated Output voltage adjustment Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Function group 1 F39 Output voltage adjustment 40 110 100 This function is ...

Страница 85: ...gher than required it may cause motor overheating due to over energizing Auto Torque Boost Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Function group 1 F27 Torque boost select 1 0 1 0 H34 No Load Motor Current 0 1 12 A H41 Auto tuning 0 0 1 0 Function group 2 H42 Stator resistance Rs 0 5 0 Ω Before Auto Torque Boost setting H34 and H42 should be set correctly See...

Страница 86: ... Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Function group 1 F4 Stop mode select 1 0 2 0 Set F30 to 1 DC brake to stop See page 10 1 for more Free run to stop Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit Function group 1 F4 Stop mode select 2 0 2 0 Set F30 to 2 Free run to stop The inverter turns off the output frequency and vol...

Страница 87: ...requency limit based on frequency High Low limit Group LED Display Parameter Name Set Value Min Max Range Factory Defaults Unit F24 Frequency High Low limit select 1 0 1 0 F25 Frequency high limit 0 400 60 0 Hz Function group 1 F26 Frequency low limit 0 400 0 5 Hz Set F24 to 1 Active run frequency can be set within the range set in F25 and F26 When frequency setting is done via Analog input voltag...

Страница 88: ...be set with the skip frequencies set to either the top or bottom point of each area However during acceleration or deceleration the run frequency within the set area is valid In the case of increasing frequency setting as shown above if frequency set value Analog setting via voltage current or digital setting via keypad is within the range of Skip frequency it maintains Skip frequency low limit va...

Страница 89: ...e F 9 Inverter will wait for this time after F8 DC Brake start frequency before applying F10 DC Brake voltage F10 It sets the level as a percent of H33 Motor rated current F11 It sets the time that F10 DC Brake voltage is applied to the motor after F 9 DC Brake wait time Caution If excessive DC Brake voltage is set or DC Brake time is set too long it may cause motor overheating and damage to the m...

Страница 90: ...F13 DC Brake start time the frequency is increasing after DC voltage is applied until the time t In this case DC Brake start time may be longer than the set value DC brake at a stop Group LED Display Parameter Name Set value Min Max Range Factory Defaults Unit Function group 1 F12 DC Brake start voltage 0 200 50 I O group I22 Multi function input terminal P3 define 11 0 24 2 F12 Set as a percent o...

Страница 91: ...ng the Multi function input terminal P1 thru P5 to use for this setting If P3 is set for Jog operation set I22 to 4 Jog Jog frequency can be set within the range of F21 Max frequency and F22 Start frequency Jog operation overrides all other operations except Dwell operation Therefore if Jog frequency command is entered in the middle of Multi Step Up Down or 3 wire operation operation is executed a...

Страница 92: ...among P1 thru P5 If P4 and P5 are selected set I23 and I24 to 15 Frequency Up command and 16 Frequency Down command respectively 10 4 3 Wire Operation Group LED display Parameter name Set value Min Max range Factory defaults Unit I20 Multi function input terminal P1 define 0 2 I O group I24 Multi function input terminal P5 define 17 0 24 4 Select the terminal among P1 thru P5 for use as 3 Wire ope...

Страница 93: ... sec In this setting motor begins to accelerate after dwell operation is executed for dwell time at the dwell frequency It is mainly used to release mechanical brake in elevators after operating at dwell frequency Dwell frequency This function is used to output torque in an intended direction It is useful in hoisting applications to get enough torque before releasing a mechanical brake Rated Slip ...

Страница 94: ...A H36 Motor efficiency 50 100 H37 Load inertia rate 0 2 0 Function group 2 H40 Control mode select 1 0 3 0 Set H40 Control mode select to 1 Slip compensation This function enables the motor to run in constant speed by compensating inherent slip in an induction motor If motor shaft speed decreases significantly under heavy loads then this value should be increased H30 Set the motor type connected t...

Страница 95: ...removed Enter 50 of the rated motor current when it is difficult to measure the motor no load current H36 Enter motor efficiency on the nameplate H37 Select load inertia based on motor inertia as shown below 0 Less than 10 times motor inertia 1 About 10 times motor inertia H37 Load inertia rate 2 Greater than 10 times motor inertia As the loads are heavier the speed gap between rated RPM and synch...

Страница 96: ... Select the feedback type of PID controller 0 Terminal I input 0 20 mA H50 PID feedback select 1 Terminal V1 input 0 10 V H51 Set the percentage of output to error If P Gain is set to 50 50 of the error value will be output H52 Set the time needed to output the accumulated error value Set the time required to output 100 when the error value is 100 If H52 Integral time for PID controller I gain is ...

Страница 97: ... Keypad setting 1 0 I V 1 V0 Potentiometer Keypa d settin g 2 P1 P5 Accel Decel 0 1 2 3 4 Analog input filter Analog input scale V 1 I Feedback select 0 1 Feed Forward Gain PID to Commercial Bypass PID output freq limit 0 1 3 I O group I20 I24 Func group2 H55 Func group2 H54 Func group2 H51 P Gain H52 I time H53 D time DRV group Frq Func group2 H50 I O group I 2 I15 I O group I 7 I15 I O group I 1...

Страница 98: ...et to 1 and press the Prog Ent key Auto tuning is activated and TUn will appear on the LED keypad When finished H41 will be displayed H42 H44 The values of motor stator resistance and leakage inductance detected in H41 are displayed respectively When H93 Parameter initialize is done the preset value corresponding to motor type H30 will be displayed Press the STOP RST key on the keypad or turn on t...

Страница 99: ...orless vector control Ensure that the following parameters are entered correctly for high perfomance in Sonsorless vector control H30 Select motor type connected to inverter output H32 Enter rated slip frequency based on motor nameplate RPM and rated frequency H33 Enter motor nameplate rated current H34 After removing the motor load select H40 Control mode select to 0 V F control and run the motor...

Страница 100: ...ax output voltage For fan or pump applications energy consumption can be dramatically reduced by decreasing the output voltage when light or no load is connected 10 11 Speed Search Group LED Display Parameter Name Set value Min Max Range Factory Defaults Unit H22 Speed Search Select 0 15 0 H23 Current level during Speed search 80 200 100 H24 P gain during Speed search 100 Function group 2 H25 I ga...

Страница 101: ...ng Acceleration Bit 3 Bit 2 Bit 1 Bit 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 H22 Speed search select 15 H23 It limits the current during Speed search Set as the percent of H33 Motor rated current H24 H25 Speed search is activated via PI control Adjust P gain and I gain corresponding to the load characteristics I54 I55 Signal of active Speed search is given to external sequence via Multi function out...

Страница 102: ...ent is greater than the preset level in H23 the rise in voltage will stop and the frequency is decreased t2 If the opposite of t1 occurs the increase in voltage starts again and the decrease in frequency stops When the frequency and voltage are restored back to the nominal level acceleration will continue at the frequency before trip Speed search is suitable operation when load inertia is great It...

Страница 103: ...numbers the preset restart try auto restart function is deactivated If the setting is reset via the control terminal or the STOP RST key on the keypad the number of auto restart try set by user is automatically entered If there is no more trip occurring for 30 sec after Auto restart operation the H26 is restored to the preset value When operation is stopped due to Low voltage Lvt or Emergency stop...

Страница 104: ...time 0 6000 5 0 Sec H82 2 nd motor Decel time 10 0 Sec H83 2 nd motor base frequency 30 400 60 0 Hz H84 2 nd motor V F pattern 0 2 0 H85 2 nd motor forward torque boost 0 15 5 H86 2 nd motor reverse torque boost 5 H87 2 nd motor stall prevention level 30 200 150 H88 2 nd motor Electronic thermal level for 1 min 50 200 150 H89 2 nd motor Electronic thermal level for continuous 100 Function group 2 ...

Страница 105: ...stopped Parameters from H81 to H90 are applied to the 1 st motor as well as the 2 nd motor 10 14 Parameter initialize Lock Parameter initialize Group LED Display Parameter Name Min Max Range Factory Default H93 Parameter initialize 0 0 1 Initialize all 4 parameter groups 2 Initialize Drive group Only 3 Initialize Function group 1 Only 4 Initialize Function group 2 Only Function group 2 5 Initializ...

Страница 106: ...ED Display 1 Jump to H94 Password Register H94 2 Press the Prog Ent z key twice 0 3 Enter the password you wish e g 123 123 4 123 is blinking by pressing the Prog Ent z key 123 4 Press the Prog Ent z key once to enter the value into memory H94 Follow the table below to change the password Current PW 123 New PW 456 Step Description LED Display 1 Jump to H94 Password Register H94 2 Press the Prog En...

Страница 107: ... UL Unlock status While seeing this message UL 4 Enter the Prog Ent z key 0 5 Enter the password created in H94 e g 123 123 6 Enter the Prog Ent z key L 7 Parameter value cannot be changed in L Lock status L 8 Press either the left W or right X key H95 See the table below to unlock the user set parameter via password Step Description LED Display 1 Go to H94 Password register H94 2 Press the Prog E...

Страница 108: ...10 Advanced functions 10 20 SV iC5 Notes ...

Страница 109: ...tored in rPM When H40 is set to 0 V F control or 1 PID control the Inverter output frequency f is displayed in RPM using the formula below Motor slip is not considered H31 Enter the number of rated motor poles on the nameplate H74 This parameter is used to change the motor speed display to rotating speed r min or mechanical speed m mi Inverter DC Link Voltage Group LED Display Parameter Name Set v...

Страница 110: ...lect 2 Torque Enter motor efficiency indicated on motor nameplate to H36 to display correct torque Power on display Group LED display Parameter Name Setting Factory default H72 Power on display 0 Frequency command 0 0 1 Accel time ACC 2 Decel time DEC 3 Drive mode drv 4 Frequency mode Frq 5 Multi step frequency 1 6 Multi step frequency 2 7 Multi step frequency 3 8 Output current CUr 9 Motor rpm rP...

Страница 111: ...e following is displayed when P1 P3 P4 are ON and P2 P5 are OFF Output terminal status monitoring Group LED Display Parameter Name Set value Min Max range Factory default Unit I O group I26 Output terminal status display Current status ON OFF of the Multi function output terminal MO and Multi function relay can be monitored in I26 The following is displayed when Multi function output terminal MO i...

Страница 112: ...g constant run Fault History Monitoring Group LED Display Parameter Name Set value Min Max range Factory default Unit I O group H 1 Fault history 1 H 5 Fault history 5 H 6 Reset fault history 0 1 0 H 1 H 5 Up to 5 fault information is stored H 6 Previous fault information stored in the code H1 thru H5 is all cleared When a fault occurs during operation it can be monitored in the nOn When the fault...

Страница 113: ... selectable and adjustable I50 The selected item will be output to Analog output terminal AM 10V 0 Output frequency Max Frequency F21 1 Output current 150 of Inverter rated current 2 Output voltage 282 Vac I50 Analog output item select 3 Inverter DC link voltage 400 Vdc I51 If you want to use Analog output value as a gauge input the value can be adjustable corresponding to various gauge specificat...

Страница 114: ...ll STALL 8 Over voltage trip OV 9 Low voltage trip LV 10 Inverter heatsink overheat OH 11 Command loss 12 During run 13 During stop 14 During constant run 15 During speed searching 16 Wait time for run signal input 17 Fault output 12 I56 Fault relay output When setting the H26 Number of auto restart tries When the trip other than low voltage trip occurs When the low voltage trip occurs Bit 2 Bit 1...

Страница 115: ...requency Detection Bandwidth 0 400 10 0 Hz Cannot be set above Max frequency F21 When setting I53 to 10 0 1 FDT 2 It activates when the preset frequency matches frequency detection level I52 and FDT 1 condition is met Active condition Preset frequency FDT level FDT 1 Group LED Display Parameter Name Set value Min Max range Factory default Unit I52 Frequency Detection Level 30 0 I O group I53 Frequ...

Страница 116: ... frequency When setting I52 and I53 to 30 0Hz and 10 0 Hz respectively 3 FDT 4 Become active when run frequency meets the following condition Active condition Accel time Run Frequency FDT Level Decel time Run Frequency FDT Level FDT Bandwidth 2 Group LED Display Description Set value Min Max range Factory default Unit I O group I52 Frequency Detection level 30 0 I53 Frequency Detection Bandwidth 0...

Страница 117: ...ency When setting I52 I53 to 30 0 Hz and 10 0Hz respectively 5 Overload OL Refer to Page 12 2 Overload Warning and trip 6 Inverter Overload IOL Refer to Page 12 6 Inverter Overload 7 Motor Stall STALL Refer to Page 12 3 Stall prevention 8 Over voltage Trip Ovt Become active when DC link voltage exceeded 400V and led to Over voltage trip 9 Low voltage Trip Lvt Become active when DC link voltage dec...

Страница 118: ... speed searching Refer to Page 10 12 Speed search operation 16 Wait time for run signal input This function becomes active during normal operation and that the inverter waits for active run command from external sequence 17 Fault relay output The parameter set in I56 is activated For example if setting I55 I56 to 17 and 2 respectively Multi function output relay will become active when trip other ...

Страница 119: ... Enter the value of max current that is capable of flowing to the motor continuously for one minute It is set in percent of motor rated current The value cannot be set lower than F52 F52 Enter the amount of current for continuous operation Normally motor rated current is used It cannot be set greater than F51 F53 For an inductance motor cooling effects decrease when a motor is running at low speed...

Страница 120: ... 1 F55 Overload warning time 0 30 10 Sec I54 Multi function output terminal select 5 12 I O group I55 Multi function relay select 5 0 17 17 Select one output terminal for this function between MO and 30AC If selecting MO as output terminal set I54 to 5 Overload OL F54 Set the value as a percent of motor rated current Current F51 F52 60 ETH trip time sec Current Multi function output F54 t Overload...

Страница 121: ...put terminal select 7 12 I O group I55 Multi function relay select 7 0 17 17 During acceleration Motor acceleration is stopped when current exceeding the value set in F60 flows During constant run Motor decelerates when current exceeding the value set in F60 flows During deceleration Motor deceleration is stopped when inverter DC link voltage rises above a certain voltage level F60 The value is se...

Страница 122: ...ion or deceleration Accel Decel time may take longer than the user setting time When stall prevention is activated during constant run t1 t2 executed in accordance with the value set in ACC Accel time and dEC Decel time Current Freq During acceleration During constant run F60 t1 t2 Multi functi on output or relay DC voltage Freq During deceleration Multi function output or relay ...

Страница 123: ... Set Value Min Max setting Factory default Unit I20 Multi function input terminal P1 define 0 I23 Multi function input terminal P4 define 18 3 I O group I24 Multi function input terminal P5 define 19 0 24 4 Select a terminal among P1 thru P5 to output external trip signal Set I23 and I24 to 18 and 19 to define P4 and P5 as External A contact and B contact External trip signal input A contact N O T...

Страница 124: ...flows Multi function output terminal MO or Multi function relay 30AC is used as the alarm signal output during inverter overload trip Group LED display Parameter Name Set value Min Max Range Factory default Unit I54 Multi function output terminal select 7 12 I O group I55 Multi function relay select 7 0 17 17 P4 A contact Frequency Run command P5 B contact ...

Страница 125: ...nal loss when frequency reference is given by V1 I V1 I or Communication option 0 Disabled Does not check the analog input signal loss 1 When less than the value set in I 2 I 7 I 12 is entered I16 Criteria for analog input signal loss 2 When below the value set in I 2 I 7 I 12 is entered EX 1 The inverter determines that the freq reference is lost when DRV Frq is set to 3 Analog V1 input I 16 to 1...

Страница 126: ...I62 Drive mode select after loss of frequency command 2 Decel to stop I54 I55 Multi function output terminal MO or Multi function relay output 30AC is used to output information on loss of frequency command to external sequence For example when I62 is set to 2 I63 to 5 0 sec and I54 to 11 respectively Freq MO Run command Set freq 5 sec ...

Страница 127: ... sink overheats due to a damaged cooling fan or an alien substance in the cooling fan by detecting the temperature of the heat sink DC link capacitor overload The inverter turns off its output when it is time to replace the old DC link capacitor to a new one Output Phase loss The inverter turns off its output when the one or more of the output U V W phase is open The inverter detects the output cu...

Страница 128: ...on Instant cut off Caution The inverter starts to regular operation when turning off the Est terminal while FX or RX terminal is ON External fault A contact input When multi function input terminal I20 I24 is set to 19 External fault signal input A Normal Open Contact the inverter turns off the output External fault B contact input When multi function input terminal I20 I24 is set to 19 External f...

Страница 129: ...heck for alien substances clogged in the heat sink Replace the old cooling fan with a new one Keep ambient temperature under 40 C Output Phase loss Faulty contact of magnetic switch at output Faulty output wiring Make connection of magnetic switch at output of the inverter securely Check output wiring Cooling fan fault An alien substance is clogged in a ventilating slot Inverter has been in use wi...

Страница 130: ... fault B in I20 I24 in I O group is ON Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input Operating method when the frequency command is lost No frequency command is applied to V1 and I Check the wiring of V1 and I and frequency reference level Parameter save error Hardware fault Communication Error Contact your local LGIS sales representa...

Страница 131: ...y become loose due to vibration temperature changes etc Check that they are tightened securely and retighten as necessary Alien substances are clogged in the cooling system Clean it using the air Check the rotating condition of the cooling fan the condition of capacitors and the connections with the magnetic contactor Replace them if there are any abnormalities 13 5 Part replacements The inverter ...

Страница 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...

Страница 133: ... V F Ratio Linear Squared Pattern User V F Overload capacity Software 150 for 60 s Torque boost Auto Manual torque boost Operation Operation mode Keypad Terminal Communication option selectable Frequency setting Analog 0 10 V 0 20 mA Keypad Potentiometer Digital Keypad Operation features PID control Up Down operation 3 wire operation Input Multi function terminal NPN PNP selectable Function refer ...

Страница 134: ...mmunication error Loss of frequency command H W fault Alarm Conditions Stall prevention Overload Momentary power loss Less than 15 msec Continuous operation More than 15 msec Auto Restart enable Environment Cooling method Forced air cooling Degree of protection Open Pollution degree 2 Ambient temperature 10 C 50 C Storage temperature 20 C 65 C Relative humidity Less than 90 no condensation Altitud...

Страница 135: ... ambient temp If the unit is installed in a panel install it where heat dissipation is properly done to keep the panel ambient temp within permissible range 2 This derating curve is based on inverter current rating when rated motor is connected 1kHz 15kHz 100 Load Current 1kHz 15kHz 100 Load Current Carrier freq Carrier freq 80 8kHz For 0 4kW 0 8kW 1 5kW inverter For 2 2kW inverter ...

Страница 136: ......

Страница 137: ...nt Inverter Power Conversion Equipment Model Name SV iC5 Series Trade Mark LG Industrial Systems Co Ltd Representative LG International Deutschland GmbH Address Lyoner Strasse 15 60528 Frankfurt am Main Germany Manufacturer LG Industrial Systems Co Ltd Address 181 Samsung Ri Mokchon Eup Chonan Chungnam 330 845 Korea We the undersigned hereby declare that equipment specified above conforms to the D...

Страница 138: ...arge immunity test Electromagnetic compatibility EMC Part 4 3 Testing and measurement techniques Radiated radio frequency electromagnetic field immunity test Electromagnetic compatibility EMC Part 4 4 Testing and measurement techniques Electrical fast transients burst immunity test Electromagnetic compatibility EMC Part 4 5 Testing and measurement techniques Surge immunity test Electromagnetic com...

Страница 139: ...ngths are kept as short as possible and that incoming mains and outgoing motor cables are kept well separated CE Mark No Models Description Interface Module1 Interface Module 2 EMC LVD 1 SV004iC5 1F AC Drive 0 5HP 220V 1 phase Yes 1 2 SV008iC5 1F AC Drive 1HP 220V 1 phase Yes 2 3 SV015iC5 1F AC Drive 2HP 220V 1 phase Yes 3 4 SV022iC5 1F AC Drive 3HP 220V 1 phase Yes 4 5 SV004iC5 1 AC Drive 0 5HP 2...

Страница 140: ...iv Revision History No Revision Date Remarks 1 First Edition 2002 12 S W Version 1 3 2 S W version update 2003 10 S W Version 1 5 ...

Страница 141: ...strial Systems Co Ltd LGIS constantly endeavors to improve its product so that information in this manual is subject to change without notice Visit Our Website http www lgis com June 2003 Publication 10310000387 ...