3. TEMPORARY START-UP:
A.
Install jumpers between the following terminals:
•
"J0" and "J5" (bypass security line);
•
"J5" and "J9" (if there is no car top inspection box);
•
"J9" and "J10" (car stop);
•
"J11" and "LNH" (normal up limit);
•
"J11" and "LNB" (normal down limit);
•
Put the hoistway door bypass switch to bypass position (hall doors closed), (hall doors locked
if manual doors or motorised cam);
•
Put the car door bypass switch to bypass position (car door closed);
•
"LTT" and "PCH" (Top travelling inspection switch). This jumper should be factory installed,
depending on the controller, please refer to prints;
•
“COM” and “SH” and “CT” (Motor thermal contact and overheating oil sensor);
B.
Set the pump motor overload module
•
If Across the Line starter: Set the overload relay according to motor FLA, as specified on the
motor nameplate.
•
If Star-Delta starter: Set the overload relay according to the motor FLA x 0.572.
Example: FLA = 22AMP 22 x 0.572 = 12.5AMP
•
If Solid-State starter (
Benshaw
):
➢
Set the parameter P1 according to motor FLA.
➢
Set the parameter P74 (Starter Type) at:
ID:
If 1 motor connect in Star-Delta (6 wires)
NOR: If 1 motor connect Across the Line (3 wires)
NOR: If 2 motors.
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...