10-5
Alarms #:
Description:
Causes et verifications
HR7911
Custom, refer to user manual list.
HR7912
Custom, refer to user manual list.
HR7913
Custom, refer to user manual list.
HR7914
Custom, refer to user manual list.
HR7915
Custom, refer to user manual list.
HR8000
Low oil level detected. (The elevator returns to main floor)
Check the oil level in the tank.
HR8001
Custom, refer to user manual list.
HR8002
Excessive travel time.
The elevator has moved at low speed. Verify LRH /
LRB mechanical switches. Verify the switches that
energize the valves. Ensure the valves are proper
functioning.
HR8003
Phase loss / reversed detection
Verify the controller’s main input voltage, supply and
the RPR relay contact.
HR8004
Weight sensor LW2 was activated.
Verify the weight load device that activated the LW2
input.
HR8005
Overheating motor thermal contact CT
Verify the motor's condition and the state of the thermal
contact (input CT).
HR8006
Overheating oil sensor detection OILO.
Verify the state of the thermal sensor that activated the
input OILO.
HR8007
One of the 2 door zone sensors "DZO" and "DZO1" remained
activated out of the levelling zone.
Verify the tape head. The sensor remained activated.
HR8008
"DZO" and "DZO1" door zone sensor did not operate properly in
levelling zone.
Verify the tape head. The sensor did not activate.
HR8009
Overload motor relay detection RS1.
Verify the state and/or the adjustment of the relay RS1.
HR8010
LU Levelling Up sensor did not operate properly in levelling
zone.
Verify the relay and sensor operation in the top of car
reader connecting box.
HR8011
LD Levelling Down sensor did not operate properly in levelling
zone.
Verify the relay and sensor operation in the top of car
reader connecting box.
HR8012
DCL switch did not open when front door closed.
Verify DCL switch operation. The switch did not open
before the DM0032 delay, when front door closed, with
HDC and CDC switches closed.
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...