10-6
Alarms #:
Description:
Causes et verifications
HR8013
DCL did not close when front door opened.
Verify DCL switch operation. The switch did not close
when the front door opened, with DOL switch opened,
CDC and HDC switches closed. The DCL switch
opened more than a half second while the front door
was completely opened.
HR8014
DOL switch did not open when front door opened.
Verify DOL switch operation. The switch did not open
when the front door is completely opened, or the door
did not completely open after 12 seconds on door
opening instruction when DCL switch and OP relay are
closed.
HR8015
DOL switch did not close when front door closed.
Verify DOL switch operation. The switch did not close
when the front door closed, with DCL switch opened
and HDC closed.
HR8100
RDCL switch did not open when rear door closed.
Verify RDCL switch operation. The switch did not open
before DM0032 delay when rear door is closing, with
CDC and HDC switches closed.
HR8101
RDCL switch did not close when rear door opened.
Verify RDCL switch operation. The switch did not
close when rear door opened, RDOL switches opened,
CDC and HDC switches closed. The RDCL switch
opened more than a half second while the rear door was
completely opened.
HR8102
RDOL switch did not open when rear door opened.
Verify RDOL switch operation. The switch did not
open when rear door opened or the door did not fully
open after 12 seconds on door opening instruction when
RDCL switch and ROP relay are closed.
HR8103
RDOL switch did not close when rear door closed
Verify RDOL switch operation. The switch did not
close when rear door closed, with RDCL switches
opened and HDC closed.
HR8104
HDC landing doors contact did not close when doors closed.
Verify HDC landing doors contact. The contact did not
close when door was fully closed, after 20 seconds,
DCL and RDCL opened CL and RCL relays activated.
Verify DCL and RDCL switches operations.
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...