3-3
•
If Solid-State starter (
Siemens
):
When the soft-starter is powered, it automatically detects the connection of the motor
(
IN DELTA
or
IN LINE
). In the
Configuration
menu, the
Rated Amps
parameter
will indicate the type of connection of the motor
Exemple: 30 HP 600 volts 32 amps motor
Rated Amps = 32A
IN LINE
Rated Amps = 18.48A
IN DELTA
(32 amps ÷ 1.732 = 18.48 amps)
In the Parameter menu, adjust the following 2 parameters:
•
Overload Amps
, enter the rated motor current (
FLA
) from the motor’s
nameplate.
•
Starting Amps,
enter 4x the value of the
Overload Amps
parameter.
Exemple: 30 HP 600 volts 32 amps motor
➔
32 X 4 = 128 Amps.
It is very important to validate the 2 parameters above, depending on the
connection of the motor, the soft-starter processor could automatically change
these downwards.
If the UTS output takes too much time to activate when starting the pump, check
the Starting Amps parameter.
C.
Connect pumping unit to the controller (pump motor, valve, etc...)
D.
Connect the main power supply to L1, L2 and L3 terminals from the main switch.
Remove the 3 fuses and measure the voltage.
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...