10-7
Alarms #:
Description:
Causes et verifications
HR8105
CDC car doors contact did not close when doors closed
Verify CDC car doors contact. The contact did not close
when door was fully closed, after 20 seconds, DCL and
RDCL opened CL and RCL relays activated. Verify
DCL and RDCL switches operations.
HR8106
CDC or HDC contacts did not open when doors opened.
Verify CDC and HDC operation. CDC and HDC
contacts did not open when doors opened, DCL and
RDCL switches opened. Verify if either contact is
short-circuited or DCL and RDCL switches operation.
This fault can occur if those switches are not opened
when HDC and CDC are fully closed.
HR8107
Front door did not close completely after 5 attempts.
Verify doorway. Something might be blocking. Check
HDC and CDC contacts operation. Also check DCL
switch operation.
HR8108
Rear door did not close completely after 5 attempts.
Verify doorway. Something might be blocking. Check
HDC and CDC contacts operation. Also check RDCL
switch operation.
HR8109
Water detection in the hoistway
Water in the hoistway or verify the float switch.
HR8110
Down valve failure.
The elevator exceeded the travelling delay while
starting in down direction. Check the valves' circuits.
Ensure the valves proper functioning.
HR8111
J9 security line was opened.
J9 security line opened while the elevator was moving
or 4 seconds after it had stopped. Verify security line
switches (see drawings for more details).
HR8112
Solid state starter (soft-start) fault.
Refer to solid state starter user manual to access the
error list.
HR8113
C3 or UC (if Soft-start) contactor failure or phase loss/reversed
detection.
On up command, verify the contactor C3 or UC (if Soft-
start) and the phase detection relay "RPR".
HR8114
The low pressure switch was activated
Verify the low pressure switch (LPS) and the pressure
in the line between the cylinder and the valve.
HR8115
Following guide is activated.
Verify the following guide switch on the hydraulic
cylinder.
HR8200
Perforated tape reader malfunction.
The processor receives too many or not enough pulses
from the perforated tape. Verify HT1 and HT2
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...