8-24
8.2.1. Motor Protections:
OPTION
DESCRIPTION
UNIT
DM
DEACTIVATE
THM
THERMAL CONTACT
Deactivation of motor temperature protection
"THM" input.
YES/NO
0183
TOO LONG TRAVEL
PROTECTION DELAY
Maximum time permitted to get to another floor.
That time needs to be long enough to move from
bottom to top floor plus a safety margin.
0.1s
0008
INVERT
LOW
OIL
SENSOR CONTACT
Reverse or not the polarity for the low oil sensor
YES/NO
0280
DEACTIVATE
LOW
PRESSURE SW. LPS
Deactivation of the low pressure switch input
(LPS).
YES/NO
0116
8.2.2. Start & Stop fine tuning:
OPTION
DESCRIPTION
UNIT
DM
N/A
8.2.3. Brake timers & Protections:
OPTION
DESCRIPTION
UNIT
DM
N/A
8.2.4. Motor control pumps, valves:
OPTION
DESCRIPTION
UNIT
DM
FAST VALVE IN
CONTROLLER
INSPECTION
The elevator will move with fast valves when
the inside controller inspection switch is
activated. If NO, only the slow speed valves will
be used.
YES/NO
0129
FAST VALVE CAR TOP
INSP & ACCES
The elevator will move with fast valves on top
of car inspection or access operation. If NO,
only the slow speed valves will be used.
YES/NO
0130
DELAY FOR PUMP
SMOOTH STOP
Delay that maintains motor rotation after the up
valves turn off. That delay avoids a kick in the
oil pipes.
0.1s
0009
NIGHT MODE
ACTIVATION DELAY
Delay before the controller switch in night mode
operation. Once the night mode turns on, when
the levelling up sensor turns on to re-level the
car, a counter delayed the car movement for one
or 2 minutes. Note: as soon the car leaves the
door zone or any trouble occurs, the night mode
is cancelled.
Minute
0052
NIGHT MODE
LEVELING DELAY
Night mode delay before LU levelling sensor
move the car UP to the floor.
Minute
0053
Содержание 2000 Series
Страница 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Страница 2: ......
Страница 5: ......
Страница 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Страница 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Страница 28: ...6 3 Standard tape selector installation ...
Страница 33: ...6 8 FIG 5 Complete installation of the selector tape and magnetic reader see Fig 6 FIG 6 Plastic guideshoe ...
Страница 44: ...6 19 ...
Страница 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Страница 60: ...10 2 ...
Страница 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...