background image

69

UMG 509

Voltage

Drop

A voltage drop is set in % of the rated voltage.

Voltage swell

The voltage swell is set in % of the rated voltage.

Current

Overcurrent

The rapid increase of current is set in % of the nominal 
current.

Adopt L2-L4

The monitoring of events can be adjusted for each 
phase. You can adopt these settings from phase L1 
and apply them to phases L2, L3 and L4.

•  No

 - The settings from phase L1 will not be applied 

to phases L2, L3 and L4 

•  Yes

 - The settings from phase L1 will be applied 

to phases L2, L3 and L4

C

Lead time

You can only set the lead time with 
GridVis.
Factory default setting: 0

C

After-run

You can only set the after-run with 
GridVis.
Factory default setting: 0

Содержание UMG 509

Страница 1: ...UMG 509 Operation manual and technical data Part no 33 03 194 Janitza electronics GmbH Vor dem Polst ck 1 D 35633 Lahnau Support Tel 0049 6441 9642 22 Fax 0049 6441 9642 30 e mail info janitza com We...

Страница 2: ...Frequency measurement 83 Direction of the rotating field 83 Applying the measuring circuit voltage 84 Table of contents General information 4 Inspection on receipt 7 Scope of delivery UMG 509 8 Avail...

Страница 3: ...terface 90 Profibus 92 Digital in outputs 96 Service and maintenance 102 Service 102 Device calibration 102 Calibration intervals 102 Firmware update 103 Battery 103 Technical data 106 Function parame...

Страница 4: ...oduced in whole or in part by mechanical or electronic means nor otherwise duplicated or republished without the binding written permission of Janitza electronics GmbH Vor dem Polst ck 1 D 35633 Lahna...

Страница 5: ...se note Please pay attention to the documentation This symbol is intended to warn you of potential dangers which could occur during installation commissioning and use C Note Ground wire connection Ind...

Страница 6: ...the product and thus excludes the warranty for covering possible damage resulting from this This device must only be operated and repaired by specialised personnel Specialised personnel are persons t...

Страница 7: ...to operation again Packing and unpacking must be carried out with customary care without the use of force and only using suitable tools The devices should be visually checked for flawless mechanical c...

Страница 8: ...minal pluggable 8 pole current measurement 1 4 1 10 01 873 Screw type terminal pluggable 6 pole digital inputs outputs 1 10 01 888 Screw type terminal pluggable 7 pole RCM thermistor input 1 10 01 859...

Страница 9: ...rmers The measurement results can be displayed saved and read out and further processed via the interfaces Ethernet Modbus Profibus The UMG 509 can be used in industrial and domestic settings By conti...

Страница 10: ...temperature range 10 C 55 C Measurement Measurement in TN and TT networks Continuous sampling of the voltage and current measurement inputs at 20 kHz Acquisition of transients 50 s and storage of up t...

Страница 11: ...s list The list can be called up via the device s home page and can be found on the enclosed CD This operation manual only describes how to operate the UMG 509 using the buttons The GridVis programmin...

Страница 12: ...Connection of a UMG 96RM via a UMG 509 as a gateway gedrehtes Patchkabel UMG 509 Direct connection of a UMG 509 to a PC via Ethernet Connection of a UMG 509 to a PC via Ethernet gedrehtes Patchkabel U...

Страница 13: ...Mounting position To ensure adequate ventilation the UMG 509 must be installed vertically There should be separation above and below of at least 50mm with 20mm space to the sides Front panel section C...

Страница 14: ...e Ethernet cable and connector type you must install a connection area below the UMG 509 The connection area below the UMG 509 should not be smaller than 50 mm Mounting The UMG 509 is mounted in the s...

Страница 15: ...15 UMG 509...

Страница 16: ...ar side of the device via terminal blocks Before connecting the supply voltage ensure that the voltage and frequency correspond to the details on the rating plate The supply voltage must be connected...

Страница 17: ...sily accessible to the user The switch must be marked as the circuit breaker for this device Voltages which are over the permitted voltage range can destroy the device c Please note The inputs for the...

Страница 18: ...o the housing potential is measured and the input impedance of the device creates residual current against the earth The residual current can trigger the insulation monitoring in IT networks The conne...

Страница 19: ...V 208V 127V 220V 220V 380V 230V 400V 240V 415V 260V 440V 277V 480V 347V 600V 400V 690V 417V 720V Maximum system rated voltage Fig Table for network rated voltages i a w EN60664 1 2003 suitable for the...

Страница 20: ...he mains frequency for the measurement and calculation of measured values The UMG 509 is suitable for measurements in networks whose mains frequency is in the range 40Hz to 70Hz For measurement with t...

Страница 21: ...ercurrent protection must have a rated value which is suitable for the short circuit current at the connection point Measured voltages and measured currents must derive from the same network c Please...

Страница 22: ...V4 Vref 3p 4wu L1 L2 L3 N V1 V2 V3 V4 Vref 3p 4w L1 L2 V1 V2 V3 V4 Vref 1p 2w L1 L2 L3 V1 V2 V3 V4 Vref p 3wu L1 L2 L3 N V1 V2 V3 V4 Vref 3p 4wu L1 L2 L3 N V1 V2 V3 V4 Vref 3p 4w L1 L2 V1 V2 V3 V4 Vre...

Страница 23: ...3 V1 V2 V3 V4 Vref 3p 3w L L L L V1 V2 V3 V4 Vref 3p 5w N V1 V2 V3 V4 Vref 3p 4wu L1 L2 V1 V2 V3 V4 Vref 1p 2w L1 L2 L3 3p 2i0 I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 3p 4w I1 I2 I3 I4 L L L L N 3p 5w I1...

Страница 24: ...2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 L1 L2 L3 N 3p 4w I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 L L L L L1 L2 L3 N 3p 2i L1 L2 1p 2i I1 I2...

Страница 25: ...25 UMG 509 3p 2i0 1p 2i I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2 L L L L N 3p 5w I1 I2 I3 I4 S1 S2 S1 S2 S1 S2 S1 S2...

Страница 26: ...3 conductor network the supporting measurement input V4 can no longer be used as a measurement input m For measurement with the supporting measurement V4 a voltage must be connected to the baseline me...

Страница 27: ...27 UMG 509...

Страница 28: ...not Any of the current measurement inputs can be loaded with 120A for 1 second Fig Current measurement I1 I3 via current transformers connection example S1 S2 L1 N PE L3 L2 S1 S2 S1 S2 S1 S2 Load c Pl...

Страница 29: ...ers the winding insulation is rated such that the current transformer can be driven open However even these current transformers are dangerous to touch when they are driven open circuit c Current tran...

Страница 30: ...S1 P1 P2 Einspeisung 1 Supply 1 Einspeisung 2 Supply 2 1P1 1P2 K L k l 1S2 1S1 1S1 1S2 2S1 2S2 2S1 2S2 k l K L 2P1 2P2 Verbraucher A Consumer A Verbraucher B Consumer B Example The current is measured...

Страница 31: ...T III and three phase 3 conductor systems with nominal network voltages up to 277V 300V CAT III according to UL 480V 300V CAT III Since the UMG 509 does not feature any integrated protection for the c...

Страница 32: ...transformers with a rated current of 30 mA is performed via the residual current transformer inputs I5 terminals 4 5 and I6 terminals 6 7 C Residual current transformer ratio The GridVis software incl...

Страница 33: ...esidual current transformer A residual current transformer should measure on isolated mains cables within a 300V CAT III network Remedy The insulation of the mains cables and the insulation of the res...

Страница 34: ...I3 L1 L2 L3 PEN N PE UMG 509 M 3 I5 I6 I4 Residual current transformers Residual current transformer Fig Example UMG 509 with residual current monitoring via measuring inputs I5 I6 Connection example...

Страница 35: ...through 10 Do not exceed the total resistance load sensor cable of 4kOhm PT100 GND VCC 10 9 8 UMG 512 Fig Example temperature measurement with a PT100 m Please note Profibus RS485 and the thermistor i...

Страница 36: ...ct Incorrect Termination resistors The cable is terminated with resistors 120Ohm 1 4W at the beginning and at the end of a segment Termination within the device is possible via the S1 DIP switch of th...

Страница 37: ...uld be used for connections via the RS485 interface Earth the screens of all cables that lead to the cabinet and at the cabinet entry Connect the screens over a generous area and in a manner that will...

Страница 38: ...Li2YCY TP 2x2x0 22 from Lapp Kabel Unitronic BUS L2 FIP 1x2x0 64 from Lapp Kabel Maximum cable length 1200m at a baud rate of 38 4k Fig Screening procedure at cabinet entry Cable Strain relief Screen...

Страница 39: ...ividual segments Devices for which the bus connection is switched on must be under current It is recommended that the master be placed at the end of a segment If the master is replaced with a bus conn...

Страница 40: ...tor e g type SUBCON Plus ProfiB AX SC from Phoenix item number 2744380 Janitza item no 13 10 539 C When using the device in a Profibus system the device address must be set using the configuration men...

Страница 41: ...erminals 2A and 2B If there are no subsequent devices in the line then the bus wiring must be terminated with a resistor switch to ON With the switch set to ON terminals 2A and 2B are switched off for...

Страница 42: ...twork through the patch cable m Please note Connection of the UMG 509 to the Ethernet may only be carried out after consulting the network administrator PC switch m Please note The UMG 509 is factory...

Страница 43: ...couplers The digital outputs have a joint reference The digital outputs can switch AC and DC loads The digital outputs are not short circuit proof Connected cables that are longer than 30m must be shi...

Страница 44: ...must have a max residual ripple of 5 C Functions for the digital outputs can be adjusted clearly in the GridVis software provided in the scope of delivery A connection between the UMG 509 and the PC...

Страница 45: ...of at least 18V and maximum 28V DC typically at 4mA is applied There is no input signal for a voltage of 0 to 5V and a current less than 0 5 mA Fig Connection of digital outputs 24V DC S1 S2 External...

Страница 46: ...ernal auxilliary voltage with an output voltage in the range 18 28V DC and a resistor of 1 5kOhm 14 15 16 2k21 2k21 2k21 2k21 2k21 Digital Input 1 Digital Input 2 UMG 509 Digital inputs 1 2 24V DC Ext...

Страница 47: ...ting device settings Labelling of the Function keys Display title Measured values Function keys Meaning of the keys Key Function Returns to the first screen home Exits selection menu Selects number Se...

Страница 48: ...ured value displays see page 120 123 By values Using the 3 and 4 keys you can select the by values of a measured value display see page 120 123 Display Voltage L L Display Communication Status Display...

Страница 49: ...red value display contains the device names and an overview of important measured values In it delivery condition the unit name consists of the device type and the serial number of the device Using th...

Страница 50: ...the main values Using the 1 home function key you always navigate to the first measured value display You would like to switch to a measured value display with by values Select the measured value disp...

Страница 51: ...sured value selection using the 6 key select The background colours for the measured value switches from grey to green The additional information is displayed in blue window Using the 2 and 5 keys sel...

Страница 52: ...displayed in blue window Using the 2 and 5 keys select the desired minimum or maximum value The time along with the date and time of the occurrence are displayed as additional information Using the 6...

Страница 53: ...ing the 4 key Navigate to the transients list using key 6 select and select a transient using the 3 or 4 keys Using the 6 key select have a transient displayed in a graph Show or hide the legend using...

Страница 54: ...2 and 5 keys scroll to the Event main value display Select the desired page using the 4 key Navigate to the event list using key 6 select and select an event using the 3 or 4 keys Using the 6 key sel...

Страница 55: ...oltage a start display appears Approximately ten seconds later the UMG 509 switches to the first Home measured value display If no display appears check whether the applied supply voltage is within th...

Страница 56: ...ration menu Using the 3 or 4 keys you select the desired submenu that can be activated using the 6 key enter Language You can set the language for the measured value displays and menus directly in the...

Страница 57: ...straightforward networks without DHCP servers BOOTP BootP enables the fully automatic integration of a UMG 509 into an existing network However BootP is an older protocol and does not provide the scop...

Страница 58: ...rresponding field can be selected via the keys 3 or 4 green marking Key 6 enter provides you with access the selection options which can then be selected with key 3 or 4 Pressing the 6 key enter again...

Страница 59: ...59 UMG 509 Measurement Configure the following here The measuring transducer for the current and voltage measurement Recording transients Recording events The mains frequency Temperature sensor...

Страница 60: ...hen measuring currents directly Setting range Primary 1 to 999999 Secondary 1 to 5 Factory default setting Primary 5 Secondary 5 Rated current The rated current defines the value to which Overcurrent...

Страница 61: ...an be used for the measurement in the neutral conductor for example 3p2i 3 phases 4 conductors 2 current transformers For networks with symmetrical loading 3p2i0 3 phases 3 conductors 2 current transf...

Страница 62: ...ransformer Setting range Primary 1 to 999 999 V Secondary 1 to 999 V Factory default setting Primary 400 V Secondary 400 V Rated voltage The rated voltage defines the value to which Transients Events...

Страница 63: ...out neutral conductor with symmetrical loading 3p3wu 3 phases 3 conductors For networks without neutral conductor with symmetrical loading 3p5w 3 phases 4 conductors Measurement at an additional outle...

Страница 64: ...minal current and voltage can be set for each phase You can adopt these settings from phase L1 and apply them to phases L2 L3 and L4 with this function No The settings from phase L1 will not be applie...

Страница 65: ...ust be set Setting range Primary 1 to 1000000 Secondary 1 Factory default setting Primary 5 Secondary 5 Monitoring Activates or deactivates the failure monitoring of the corresponding residual current...

Страница 66: ...urement inputs for transients The transient monitoring can be adjusted for each phase There are two independent criteria by which transients are detected If a transient has been detected the wave form...

Страница 67: ...points exceeds the set threshold value a transient is detected Off Transient monitoring has been switched off Automatic Factory default setting The threshold value is calculated automatically and is...

Страница 68: ...n event has occurred the corresponding measured value is recorded with the set pre run and after run periods respectively 0 1000 full waves Event records are configured with the GridVis and displayed...

Страница 69: ...toring of events can be adjusted for each phase You can adopt these settings from phase L1 and apply them to phases L2 L3 and L4 No The settings from phase L1 will not be applied to phases L2 L3 and L...

Страница 70: ...The mains frequency will be measured 50Hz The mains frequency is fixed at 50Hz The mains frequency will not be measured 60Hz The mains frequency is fixed at 60Hz The mains frequency will not be measu...

Страница 71: ...71 UMG 509 Temperature When using a temperature measurement the corresponding sensor type must be selected from a predefined list PT100 PT1000 KTY83 KTY84...

Страница 72: ...al number of the device Fixed MAC address of the device Set IP address Set gateway address Date and time Set password Reset settings C You cannot configure the date and time directly on the device You...

Страница 73: ...as already been set you must know the current password Note down the changed password When selecting the Password green marking the password can be changed using the 6 key enter and keys 2 to 5 Pressi...

Страница 74: ...g the Reset key Some specific energy meters cannot be selected Highlight the Clear energy button green marking and enable the deletion process using the key 6 enter Select Yes with the 4 key Confirm t...

Страница 75: ...max values Highlight the Min max values item green marking and enable the clear process using the key 6 enter Select Yes with the 4 key Confirm the selection using the 6 key The Carried out message a...

Страница 76: ...ings or deleted Entered activation codes are not deleted Select Yes with the 4 key Confirm using the 6 key The Carried out message appears in the line the delivery status is restored Re initialisation...

Страница 77: ...witches to the Standby brightness Setting range 60 to 9999 sec Factory default setting 900 sec Brightness standby Brightness level the system switches to after the standby time expires The standby tim...

Страница 78: ...re automatically shown one after the other This does not affect the displays of the configuration Setting range Yes no Factory default setting No Rotation interval Here you can set the time after whic...

Страница 79: ...displaying the current and voltage in the graphic representations Using the keys 3 or 4 select the desired coloured field Confirm the selection using the 6 key Using the keys 3 or 4 select the desire...

Страница 80: ...hat are subject to purchase and can be subsequently activated List of the functions that can be activated BACnet You receive the activation codes from the manufacturer The manufacturer requires the se...

Страница 81: ...tus Up to 7 customer specific Jasic programs 1 7 and a recording can run in the UMG 509 The Jasic programs can have the following statuses Stopped Running You cannot change the status of the Jasic pro...

Страница 82: ...tage The supply voltage level for the UMG 509 is specified on the rating plate After connecting the supply voltage a display appears Approximately 15 seconds later the UMG 509 switches to the first me...

Страница 83: ...nt inputs The mains frequency must be in the range from 40Hz to 70Hz If there is no sufficiently high measured voltage available the UMG 509 cannot determine the mains frequency and thus cannot perfor...

Страница 84: ...e current displayed by the UMG 509 must correspond with the input current The UMG 509 must display approx zero amperes in the short circuited current measurement inputs The current transformer ratio i...

Страница 85: ...to the correct voltage measurement input In the current measurement considered here the k and l connections are reversed or there is a return feed in the mains power supply Voltage and current only h...

Страница 86: ...g is performed using the corresponding menu item or by setting address 18895 for the residual current measurement input I5 and 18897 for I6 If there is an interruption in the connection to the current...

Страница 87: ...or connection error to the transformer The alarm bit must be reset or acknowledged manually Failure monitoring There is a connection error to the transformer Example Interruption of the connection to...

Страница 88: ...amount is correct but the sign of the power output is negative S1 k and S2 l could be inverted at the current transformer or they supply effective power back into the network Checking the communicatio...

Страница 89: ...dged The measurement range is exceeded if at least one of the four voltage or current measurement inputs lies outside their specified measuring range Threshold values for exceeding the measurement ran...

Страница 90: ...multiple coils 16 10Hex Preset multiple registers 23 17Hex Read write 4X registers Modbus functions slave 03 Read holding registers 04 Read input registers 06 Preset single register 16 10Hex Preset m...

Страница 91: ...appears as follows Name Hex Note Device address 01 UMG 509 address 1 Function 03 Read Holding Reg Start Addr Hi 4A 19000dez 4A38hex Start Addr Lo 38 Ind Value Hi 00 2dez 0002hex Ind Value Lo 02 Error...

Страница 92: ...re variables that are defined by the user in Jasic and are available to each interface in the UMG 509 Profibus Profibus profiles A Profibus profile contains the data to be exchanged between a UMG and...

Страница 93: ...ram is not required Fig Block diagram for data exchange between PLC and UMG 509 PLC PLC process output box 1 Byte Profile number 0 to 15 2 Byte Data to the UMG 509 PLC process input box 1 Byte Return...

Страница 94: ...L1 L4 Float 1 28 109 THD voltage L1 Float 1 29 113 THD voltage L2 Float 1 30 117 THD voltage L3 Float 1 Factory pre configured profiles Profibus profile number 1 Byte index Value type Value format Sca...

Страница 95: ...ive energy L3 Float 1 Profibus profile number 3 Byte index Value type Value format Scaling 1 1 Effective power L1 Float 1 2 5 Effective power L2 Float 1 3 9 Effective power L3 Float 1 4 13 Effective p...

Страница 96: ...an be configured using the GridVis software included in the scope of delivery The settings of the functions in the configuration menu must be made using the GridVis software Fig GridVis software confi...

Страница 97: ...a pulse of defined length is applied on the output after reaching a certain adjustable amount of power You need to make various adjustments in the configuration menu using the GridVis software to use...

Страница 98: ...m pulse length and the minimum pulse interval for the maximum number of pulses per hour Examples of the maximum possible number of pulses per hour Pulse length Pulse interval Max pulse h 10 ms 10 ms 1...

Страница 99: ...only be emitted when the measured value has a positive sign If you check the pulse value with a negative sign the pulses will only be produced when the measured value has a negative sign C Since the...

Страница 100: ...Voltage L N max 300 V Power per phase 150 A x 300 V 45 kW Power at 3 phases 45kW x 3 Max connected load 135kW Calculating the pulse value Fig Connection example for the circuit as pulse output 230V A...

Страница 101: ...101 UMG 509...

Страница 102: ...e legal provisions The permanently installed lithium battery must be disposed of separately Service Should questions arise which are not described in this manual please contact the manufacturer direct...

Страница 103: ...erature of 45 C The typical life expectancy of the battery is 8 to 10 years The battery type CR2450 3V can be replaced by the user Firmware update If the device is connected to a computer via Ethernet...

Страница 104: ...fell short of Install current transformer with a smaller current transformer ratio Voltage displayed is too large or too small Measurement in the wrong phase Check connection and correct if necessary...

Страница 105: ...verload Voltage and current measurement input outside the measurement range See section Measurement range exceeded Check connection and correct if necessary Use suitable voltage and current transforme...

Страница 106: ...erature K55 25 C to 70 C Relative humidity 5 to 90 RH Ambient conditions during operation The UMG 509 is intended for weather protected stationary use The UMG 509 must be connected to the protective c...

Страница 107: ...onductors Only one conductor can be connected per terminal Single core multi core fine stranded 0 2 2 5mm2 AWG 24 12 Terminal pins core end sheath 0 25 2 5mm2 Tightening torque 0 5 0 6Nm Stripping len...

Страница 108: ...rms Resolution 0 01V Crest factor 1 6 related to 600Vrms Impedance 4MOhm phase Power consumption approx 0 1VA Sampling rate 20kHz phase Transients 50 s Frequency range of the fundamental oscillation R...

Страница 109: ...tic sleeve 0 20 1 5mm2 Stripping length 7mm Tightening torque 0 20 0 25Nm Cable length up to 30m unshielded from 30m shielded Residual current monitoring RCM Rated current 30mArms Metering range 0 to...

Страница 110: ...ange Resistor range Measurement uncertainty KTY83 55 C to 175 C 500Ohm to 2 6kOhm 1 5 rng KTY84 40 C to 300 C 350Ohm to 2 6kOhm 1 5 rng PT100 99 C to 500 C 60Ohm to 180Ohm 1 5 rng PT1000 99 C to 500 C...

Страница 111: ...upply voltage 20V 30V DC SELV or PELV supply Switching voltage max 60V DC 30V AC Switching current max 50mAeff AC DC Response time Jasic program 200ms Output of voltage dips 20ms Output of voltage exc...

Страница 112: ...6kbps Termination resistor Can be activated by micro switch Profibus interface Connection SUB D 9 pole Protocol Profibus DP V0 as per EN 50170 Transmission rate 9 6k baud to 12 MBaud Ethernet interfac...

Страница 113: ...113 UMG 509...

Страница 114: ...s 0 A to 9999 kA Measured neutral conductor current IN 0 2 IEC61557 12 0 001 to 7 Arms 0 A to 9999 kA Residual currents I5 I6 IDIFF 1 IEC61557 12 0 to 40 mArms 0 A to 9999 kA Computed neutral conducto...

Страница 115: ...4 THD Ri 1 0 IEC61557 12 up to 2 5 kHz 0 to 999 Mains signal voltage interharmonics voltage MSV Declarations 1 In relation to the amplitude 2 In relation to phase and amplitude 3 In relation to funda...

Страница 116: ...nsients IEC EN 61000 4 5 2007 Surge voltages IEC EN 61000 4 6 2009 Immunity to conducted disturbances induced by radio frequency fields 0 15 80MHz IEC EN 61000 4 8 2010 Power frequency magnetic fields...

Страница 117: ...117 UMG 509...

Страница 118: ...118 UMG 509 Dimension diagrams Cut out size 138 0 8 x 138 0 8 mm Rear side Patch cable...

Страница 119: ...119 UMG 509 Side view View from below...

Страница 120: ...transducer Transients Events Nominal frequency Thermistor input System information Reset password Display Colours U I L1 L4 Extensions Activation Jasic status Measuring transducer Phase L1 L2 L3 L4 I...

Страница 121: ...values Voltage L N Current L1 to L4 Voltage L L Current Sum Main values Apparent power Overview By values Effective power Overview Tariff 1 tariff 2 Reactive power Overview Tariff 1 tariff 2 Sum Powe...

Страница 122: ...e power progression L1 L2 L3 L4 L1 to L3 L1 to L4 Reactive power progression L1 L2 L3 L4 L1 to L3 L1 to L4 Current progression L1 L2 L3 L4 Voltage progression L1 L2 L3 L4 Harmonic Voltage L1 L2 L3 L4...

Страница 123: ...123 UMG 509 Phasor diagram Oscilloscope L1 Communication status Oscilloscope L2 L3 L4 Oscilloscope ULN1 to 3 ULN1 to 4 Oscilloscope IL1 to 3 IL1 to 4 Main values By values...

Страница 124: ...1 S2 S1 S1 S2 S2 S1 S2 S1 S2 I1 19 20 S1 S2 I2 21 22 S1 S2 I3 23 24 S1 S2 I4 25 26 VN 31 L3 Hilfsenergie Auxiliary Supply 17 18 L N PE Verbraucher Loads PE N L1 RS485 B 8 9 10 Temp PT100 IPE IDIFF 0 3...

Отзывы: